Dxmr110-8K Overview - Banner DXMR110-8K Instruction Manual

Io-link master
Table of Contents

Advertisement

DXMR110-8K O
VERVIEW

2. DXMR110-8K Overview

Banner's DXMR110-8K IO-Link Master consolidates data from multiple sources to provide local data processing as well as accessibility for host
systems as a platform for the Industrial Internet of Things (IIoT).
The DXMR110-8K IO-Link Master 8-port IO-link device serves as the gateway for the connection of up to eight IO-link devices including sensors,
lighting products, IO-link hubs, and more.
The DXMR110-8K contains eight IO-link ports, allowing for concurrent communication to up to eight IO-Link devices. Data is collected into the
internal logic controller to facilitate edge processing, protocol conversion to Industrial Ethernet, Modbus/TCP, and PROFINET, and pushing infor-
mation to web servers. In addition to IO-Link devices, the IO-Link master can be used to transmit up to 16 discrete signals using pin 2 or pin 4 of
the IO-link master ports.
The configurable IO-link master device works with IO-link devices and allows for quick deployment of IO-link data to Ethernet, Modbus/TCP,
and PROFINET networks.
Local control or connectivity with automation protocols, including EtherNet, Modbus/TCP, and PROFINET
Logic processing and problem-solving capable of deploying solutions to process and control data from multiple devices
Compact housing saves space and weight compared to traditional "block" style form factors
IP67 housing simplifies installation in any location by eliminating the need for a control cabinet
Consolidate cable runs to minimize cabling and associated weight, especially in weight-critical applications such as robotics
Flexible and Customizable—Expanded internal logic controller with action rules and ScriptBasic programming
Logic Controller
Program the DXMR110-8K's logic controller using action rules and/or ScriptBasic programming languages, which can execute concurrently. The control func-
tions allow freedom when creating custom sensing and control sequences. The logic controller supports the Modbus protocol standards for data management,
ensuring seamless integration with existing automation systems. File password protection is an option.
Action Rules
Thresholds (IF/THEN/ELSE) with timers, minimum on/off time
Math/Logic Rules (arithmetic and bitwise operators)
Control Logic (logical operators and SR/T/D/JK flip flops)
Trending (multiple averaging filters)
Tracking (counts, on/off times)
Push data on conditions
Programming Language—ScriptBasic to create variables, arrays, functions, loops, IF/THEN/ELSE, logical and arithmetic operators, API commands, register
access, string functions and operators, time commands
Scheduler
Time/calendar-based events
Holiday skips
One-time events
Dynamic scheduler updating
Astronomical clock
Push to the Cloud
Register Mapping
Cyclical Read rules from wireless devices or local wired Modbus devices that include optional scaling, error conditions, and the ability
to activate a read rule
Cyclical or Change of State Write rules to local wired Modbus devices with scaling
1. EtherNet/IP™ is a trademark of ODVA, Inc. Modbus