Controller Connections For The Dxmr110-8K; Status Indicators For The Dxmr110-8K; Ethernet - Banner DXMR110-8K Instruction Manual

Io-link master
Table of Contents

Advertisement

4. Controller Connections for the DXMR110-8K

To connect IO-Link devices on machines in industrial environments, an M12 quick-disconnect connection is typically used. The pin assignment
according to IEC 60974-5 is the following:
Pin 1: 24 V DC
Pin 2: Switching Digital I/O (PNP only)
Pin 3: 0 V
Pin 4: Switching Digital I/O (NPN, PNP, or Push-Pull) and IO-link Communication Line
One male M12 connection provides common power and ground to all M12 IO-Link ports. Two100 Mbps Ethernet ports (female) use an M12
D-coded Ethernet connection.
Modbus/TCP
EtherNet/IP
PROFINET
Eight IO-Link controller connections using female M12 connectors.
Separate IO-Link control and programmability for each connection point
Configurable SIO mode on Input 1 and Input 2 of each IO-Link port
The DXMR110-8K IO-Link Master has eight Class A ports. Pin 2 on these is an additional discrete IO channel. For specific pinout connections,
see
Wiring for the DXMR110-8K on page
For more information on the device registers and port settings of the DXMR110-8K IO-Link Master, refer to the DXMR110-8K IO-Link Master
IO-Link Master Device Register Map (p/n 233478).

4.1. Status Indicators for the DXMR110-8K

The DXMR110-8K 8-Port IO-Link Hub has two LED indicators for pin 2 and pin 4 for each IO-link port to provide indication visibility. There is also
an additional amber LED indicator to indicate power to the IO-link master.
State
SIO input mode and 0V in
Off
SIO output mode and the output is turned off
Pin 2 not configured
Solid green
Flashing green
SIO input mode and 24V in
Solid amber
SIO output mode and the output is turned on
Flashing amber
Solid red
Electrical short
Flashing red

4.2. Ethernet

Before applying power to the DXMR110-8K, verify the Ethernet cable is connected.
L+
1
C/Q
4
2
3
L-
Figure 1: IO-Link pin assignments
6.
Pin 2
© Banner Engineering Corp. www.bannerengineering.com
C
ONTROLLER
IO-Link Mode (process data)
Digital I/O (DIO) Mode (ON/OFF data)
Port is disabled
SIO input mode and 0V in
SIO output mode and the output is turned off
An IO-Link device is connected
IO_Link autostart or manual mode,
No device is connected
SIO input mode and 24V in
SIO output mode and the output is turned on
Electrical short
IO_Link manual, validation mode, and the wrong device is plugged
in
C
DXMR110-8K
ONNECTIONS FOR THE
Pin 4
12

Advertisement

Table of Contents
loading

Table of Contents