Deactivated
Use deactivated mode for any unused IO-link master ports if a device is not connected.
IO-Link Manual
The IO-Link master only connects IO-Link devices that have a certain vendor ID and device ID (1: IOL_MANUAL).
This mode is also required to for the Backup and Restore or Restore function.
IO-Link Autostart
The IO-Link master connects to every connected IO-Link device (2: IOL_AUTOSTART).
Digital Input
The IO-Link port functions as a standard digital input (3: DI_C/Q).
Digital Output
The IO-Link port functions as a standard digital output (4: DO_C/Q).

1.3. Combining IO-Link Devices with Different Specifications

Any combination of masters and devices is possible. However, if IO-Link devices of a different IO-Link specification are combined, note that:
Only IO-Link v1.0 devices can be operated on the IO-Link v1.0 masters
IO-Link v1.0 and v1.1 devices can be operated on the IO-Link v1.1 masters
IO-Link devices with IO-Link specification V1.0 do not support backup and restore features (data storage).