2.3.2

Setting I/O numbers

Set the I/O numbers on the I/O Assignment tab.
(1) Purpose of I/O number assignment
(a) Reserving points for future module changes
The number of points can be flexibly set so that the I/O number modification can be avoided when
changing the current module to another in the future.
32 points can be assigned for future use to the slot where an input module with 16 points is currently
Ex.
mounted.
(b) Preventing I/O numbers from changing
The change in the I/O numbers can be prevented when an I/O module or intelligent function module, whose
occupied I/O points are other than 16, is removed due to failure.
(c) Changing the I/O numbers to those used in the program
When the I/O numbers used in the actual system differ from those in the designed program, the I/O numbers of
each module on the base unit can be changed to the ones in the designed program.
● If any of the I/O modules whose number of I/O points are other than 16 fails without I/O assignment setting, the I/O
numbers assigned following to the failed module may change, leading to a malfunction. For this reason, making the I/O
assignment setting is recommended.
● I/O assignment setting allows the following settings as well. (The I/O assignment is required for the input response time
and switch settings.)
• Input response time setting (I/O response time) (
• Error time output mode setting (
• CPU module operation setting during a hardware error of intelligent function modules (
3.9)
• Switch setting of intelligent function modules and interrupt modules (
CHAPTER 2 APPLICATION OF PROGRAMMING
Page 139, Section 3.7)
Page 141, Section 3.8)
Page 142, Section
Page 143, Section 3.10)