4.5

Module Access Devices

4.5.1

Intelligent function module device

The intelligent function module device allows direct access from the CPU module to the buffer memory of the
intelligent function modules which are mounted on the main and extension base units.
(1) Specification method and application example
(a) Specification method
Specify the I/O number and buffer memory address of the intelligent function module.
Specification method:
(b) Application example
Specify the device as shown below to store CH.1 to CH.4 digital output values of the Q64AD analog-digital
converter module into D0 to D3 of the CPU module when the Q64AD is mounted in the position of I/O number
020 (X/Y020 to X/Y02F).
If the intelligent function module device is used, device comments can be attached to the buffer memory areas.
Operating manual for the programming tool used
382
U \G
Buffer memory address (setting range: 0 to 65535 in decimal)
Starting I/O number of intelligent function module
Setting : First 2 digits of starting I/O number expressed in 3 digits
For X/Y1F0
* Setting range: 00
H
BMOV
D0
K4
U2\G11
X/Y1F0
Specification: 1F
to FF
H
Q64AD
11
CH.1 Digital output value
12
CH.2 Digital output value
13
CH.3 Digital output value
14
CH.4 Digital output value