(1) Input response time setting
Set input response time values in the I/O Assignment tab of the PLC parameter dialog box.
(2) Precautions
(a) When input response time is shortened
The shorter the input response time is, the more the CPU module is susceptible to noise.
Consider the operating environment when setting input response time values.
(b) When an AnS/A series-compatible module is used
The input response time cannot be changed.
Even if the input response time is set to the slot of the input module or interrupt module (AnS/A series-
compatible), the setting is not valid.
(c) Enabling the setting
The input response time setting will be enabled when:
• the CPU module is powered off and then on, or
• the CPU module is reset.
140
1.
Set I/O assignment.
2.
Click the
3.
Select an input response time.
button.