3.12.3

Precautions for online change

The following shows precautions for online change.
(1) Online change during boot operation
When data are written to the CPU module in the RUN status during boot operation, the status of boot source
program is not changed.
(2) Operations prohibited when programs are written to the CPU module in the
RUN status, TC setting value is changed, or data are transferred from a
program cache memory to a program memory
Do not perform the following operations.
(a) Power-off or reset
The following operations are not normally completed if they are performed during online change, TC setting
value change, or data transfer from the program cache memory to the program memory.
If performed, write the data to the CPU module again.
• Power-off
• Reset
(b) Operations from a programming tool
The following operations cannot be performed during online change, TC setting value change, or data transfer
from the program cache memory to the program memory. If performed, an error is displayed on the
programming tool. Perform the following operations after online change.
• Online change (ladder mode), online change (files)
• TC setting value change
• Data transfer to the program memory
• Write to PLC (Flash ROM)
Note 3.6
Universal
With the Universal model QCPU whose serial number (first five digits) is "12012" or later, this function can be executed
while data are being transferred from the program cache memory to the program memory.
Note 3.6
Note 3.6