4.4

Link Direct Device

The link direct device is a device for direct access to the link device in a CC-Link IE Controller Network module,
CC-Link IE Field Network master/local module or MELSECNET/H module. This CPU module can directly write data to
or read data from the link device in each network module using sequence programs, regardless of the link refresh of
the CPU module.
(1) Specification method and application example
(a) Specification method
• For a CC-Link IE Controller Network module and MELSECNET/H module, specify the device with a
network number and a device number as shown below.
• For a CC-Link IE Field Network master/local module, specify the device with a network number and a
device number as shown below.
378
Specification method: J
\
Specification method: J
\
Device No.
Input(X)
Output(Y)
Link relay(B)
B0 to 7FFF
Link register(W)
Link special relay(SB)
SB0 to 1FF
Link special register(SW)
SW0 to 1FF
Network number : 1 to 239
Device No.
Input(X)
Output(Y)
Link register(RWw)
Link register(RWr)
Link special relay(SB)
Link special register(SW)
Network number : 1 to 239
X0 to 1FFF
Y0 to 1FFF
W0 to 1FFFF
X0 to 3FFF
Y0 to 3FFF
W0 to 1FFF
W2000 to 3FFF
SB0 to 1FF
SW0 to 1FF