List Of Interrupt Pointer Numbers And Interrupt Factors - Mitsubishi Electric MELSEC-Q00U(J)CPU User Manual

Table of Contents

Advertisement

4.11.1

List of interrupt pointer numbers and interrupt factors

The list of interrupt pointer numbers and interrupt factors are shown below.
(1) When a Q series interrupt module is mounted
I No.
Interrupt factor
I0
I1
I2
I3
I4
I5
I6
I7
Interrupt by an
interrupt module
I8
(QI60)
I9
I10
I11
I12
I13
I14
I15
I16
I17
I18
I19
I20
Interrupt by a
I21
sequence-started
module
I22
I23
I24
I25
I26
I27
*5
I28
*5
I29
Interrupt by the
*1
*5
internal timer
I30
*5
I31
*1
The time-limit value of the internal timer is set by default. In the PLC system tab of the PLC parameter dialog box, the
value can be changed within the range of 0.5ms to 1000ms in increments of 0.5ms.
*2
This is available for multiple CPU system configuration.
*3
To use the intelligent function module interrupt, the intelligent function module setting (interrupt pointer setting) is
required in the PLC system tab of the PLC parameter dialog box. (For interrupt from an intelligent function module, refer
to Page 231, Section 3.22.
*4
I50 has the highest priority (priority 22), and I255 has the lowest priority (priority 227).
*5
When an interrupt occurs, even if no interrupt pointer exists on the program, CAN'T EXECUTE(I) (error code: 4220)
does not occur.
*6
To use I49, do not execute any other interrupt programs (I0 to I48, I50 to I255) nor fixed scan execution type programs.
If executed, the interrupt program (I49) will not be executed at preset intervals.
Priority
I No.
1st point
6
2nd point
7
3rd point
8
4th point
9
5th point
10
6th point
11
7th point
12
I32 to
I44
8th point
13
9th point
14
10th point
15
11th point
16
12th point
17
13th point
18
14th point
19
15th point
20
I45
16th point
21
1st module
228
2nd module
229
I46 to I48
3rd module
230
4th module
231
5th module
232
I49
6th module
233
7th module
234
8th module
235
9th module
236
10th module
237
I50 to
11th module
238
I255
12th module
239
100ms
5
40ms
4
20ms
3
10ms
2
Interrupt factor
-
Multiple CPU
*2 *5
synchronous
interrupt
-
High-speed
interrupt
Intelligent
function module
Specify an intelligent function
*3*4
interrupt
module or interrupt module (QI60)
/Interrupt by an
interrupt module
(QI60)
CHAPTER 4 DEVICES
Priority
N/A
-
0.88ms
1
N/A
-
0.1 to 1.0ms
*6
22 to 227
in parameter.
411
4

Advertisement

Table of Contents
loading

Table of Contents