Installation

4.5.3 Installation Space Requirements

Reserve enough space when installing inverter (at least 300mm) for heat
dissipation.
≥300mm
≥300mm
≥300mm
≥300mm
For multi-inverter installation scenarios, the inline installation method is
recommended; when the space is insufficient, the recommended method of
installation in the form of "products"; it is not recommended to install multiple
inverters in stacks. If you choose stack installation, please refer to the installation
separation distance below.
≥300mm
≥300mm
≥1000mm
≥300mm
≥500mm
28
Reserved space dimensions of
installation
Position
Min Distance
Left
300mm
Right
300mm
Up
300mm
Down
500mm
≥300mm
≥300mm
≥300mm
≥1000mm
≥300mm
≥300mm
≥500mm

4.6 Mounting

Preparation
Ø
Please prepare the following tools before installation.
Installation tools: screwdriver, wrench, Φ10 drill, rubber hammer, socket
wrench set and Hexagon keys.
Step 1: Fix the wall bracket to the wall
Ø
First find the expansion screw and the wall bracket in the accessory bag,
as shown below:
It consists of four parts
Expansion bolts, Tapping screws, nut, Gasket
a) Use a marker to mark drilling holes of the bracket on the wall.
b) Drill holes at marked spots with depth of 65mm.
Installation
Bracket
Gasket
29