Setting
q ) EPS(Off-grid) Setting
User can set the frequency selection in the EPS(Off-grid) mode here, and set the
minimum capacity reserved for battery discharge.
EPS(Off-grid) Setting
EPS(Off-grid) Setting
> Frequency
>Frequency
50Hz
r ) Phase Unbalanced
This function controls the distribution of AC output power.
"Enable" means each phase will be divided according to the loads connected with
each phase. "Disable" means each phase power will be divided equally and "disable"
is the default setting value.
three phase
inverter
Phase Unbalanced
3kw
4kw
5kw
Function Control
>Disable<
If 12kw AC power can be exported, each phase power will
be divided as above according to different loads connected
with each phase.
enable mode
s ) Reset
Users can reset the reset error log, meter power ,inverter power, and
restore factory settings here.
Reset Error Log
>Reset
>Reset
Yes
Reset INV Energy
>Reset
>Reset
Yes
t )Advance Password
Here you can reset the advanced password. "Set OK!" is displayed on
success, and "Setup Failed!" Will also displayed on failure.
Advance Password
Set OK!
106
EPS(Off-grid) Setting
> Min SoC
60Hz
three phase
inverter
load1
load2
load3
load1
load2
3KW
4KW
5KW
3KW
4KW
4kw
4kw
4kw
meter
If 12kw AC power can be exported, each phase power will
be divided equally as above and it is unrelated with the
loads connected with each phase.
disable mode
Reset Meter/CT_1
Reset Meter/CT_2
>Reset
Yes
Factory Reset
Yes
Advance Password
Setup failed
Ø Manufactory Setting
10%
a ) RlyEPSN Setting
The user needs to set whether the inverter is installed in Australia or
Europe. When the inverter is off the grid, the N line and PE line of the
load3
5KW
circuit in Australia need to be connected; the N line and PE line of the
European circuit need to be separated .
meter
b ) COM Port Select
Here external communication protocol or external indoor screen of
Yes
the inverter can be set. When it is used for external communication
protocol, it can choose RS485 or MOBUS.
RlyEPSN Setting
COM Port Select
RlyEPSN Setting
RlyEPSN Setting
>function Control
>function Control
Europe
RS485/MOBUS
>RS485
MOBUS
Setting
a)
b)
Australia
107