5.6 Grounding Connection (Mandatory)
The user must make two ground connections: one shell grounding,
and one equipotential grounding. This prevents electric shock.
Note: If the PV end of the inverter is not connected with earth, the
inverter will turn on a red light Inspect and report ISO Fault. This
inverter complies with IEC 62109-2 clause 13.9 for earth fault alarm
monitoring.
Ground wire port of X3-Hybrid G4 M series inverter has been
connected, and the D series needs to be wired according to the
following steps.
Ø
Ground connection steps
Step 1. Prepare a one-core cable (12AWG), and then find the ground
terminal in the accessories.
12AWG
One-core cable (12 AWG)
OT terminal
Step 2. Strip the grounding cable insulation(length"L2), insert the
striped cable into the ring terminal, and then clamp it.
Diagonal plier