WESTECH Solax X3-HYBRID G4 Manual page 53

Table of Contents

Advertisement

Setting
f ) Self Test (only for CEI 0-21)
The self test function allows users to test the following items. "Full test",
"Ovp(59.S2) test"27. "Uvp (s1) test", "Uvp (27. s2) test", "Ofp (81> .S1) test",
"Ufp (81 <.S1) test", "Ufp (81> .S2) test", "Ufp (81 <.S2) test",
"Ovp10 (59. s1) test".
In the self-test interface, the user can select "all tests" or a single test item
for testing.
Before testing, make sure that the inverter is connected to the grid.
All tests take about 6 minutes. And it will display "Success" and then "Delivery".
For a single test item, it takes about a few seconds or minutes.
Click "Test Report" to view the test results of all items.
ALL Test
Test report
Uvp(27.S1) test
>Ofp2(81>.S2)result
Ft: 51.50Hz Tt:1000ms
Fs: 0.00Hz To: 998ms
F0: 0.00Hz
pass
>Ofp2(27.S2)result
Vt: 92.0V Tt: 200ms
Vs:
0.0V To: 196ms
V0:
0.2V
pass
>Ofp2(81>S1)result
Ft: 50.50Hz Tt: 100ms
Fs:
0.00Hz To: 96ms
F0:
0.2Hz
pass
>Ufp2(81<.S2)result
Ft: 47.50Hz Tt: 400ms
Fs:
0.00Hz To: 3999ms
F0:
0.02Hz
pass
100
>Ovp2(59.S2)result
Vt: 264.5V Tt: 300ms
Vs:
0.0V To: 200ms
V0:
0.0V
pass
>Uvp2(27.S1)result
Vt: 195.5V Tt: 400ms
Vs:
0.0V To: 200ms
V0:
0.0V
pass
>Ufp2(81<.S1)result
Ft: 49.50Hz Tt: 100ms
Fs:
0.00Hz To: 98ms
F0:
0.02Hz
pass
>Ovp10(59.S1)result
Vt: 253.0V Tt: 600ms
Vs:
0.0V To: 598ms
V0:
0.0V
pass
g ) Shadow Fix
Here, you can set the shadow tracking with four options, which are off,
low, medium, and high.
Shadow Fix
>Func Select
h ) Modbus
Here you select the baud rate of the external communication protocol,
the default location of 19200 and 485 addresses.
Modbus RTU/485
Baud Rate:
115200
I ) Matebox Setting
If you want Matebox installed, you need to turn this feature on here.
Matebox Setting
>Select
Disable
Setting
>OFF<
Modbus RTU/485
RS485 Addr:
1
Enable
101