Typical Problems - Conair GB User Manual

Gb and wsb series gravimetric blenders with 12-component control
Hide thumbs Also See for GB:
Table of Contents

Advertisement

These problems are based on phone calls that we have received from
Autoweigh Blender users.
The display does not read close to zero when power is turned on, bin
empty (plus or minus 10 grams).
*
The load cells are not plugged in.
*
The weigh bin is not resting properly and freely in its platform
or the platform is not resting properly on the bolts that
protrude from the load cell enclosures.
*
The controller was never calibrated for these load cells or you
just did a CLEAR ALL.
by several hundred grams.
*
The load cells are damaged.
The Controller "RESETS" itself for no reason.
electrical noise or voltage spikes disrupting the processor.
*
See WIRING CONSIDERATIONS, ASSEMBLY section.
The ALARM is flashing and the display shows a weight above 100 or below
-50 grams.
If above 100, the Weigh bin dump valve keeps opening and
closing every 6 or 7 seconds.
*
There is material in the weigh bin that will not dump out.
*
The dump flap may be stuck.
*
The load cells are hung up or obstructed.
*
The load cells are out of calibration.
*
Incorrect grounding is causing wide load cell readouts.
The VERY FIRST DISPENSE does NOT take place.
ALARM begins to flash.
*
The air supply is not connected or the pressure is set too low.
*
The Natural solenoid is not connected properly.
*
The 1/2 amp panel front fuse is blown.
*
The NATURAL slide gate is jammed.
bent.
The NATURAL dispense valve continues to dump repeatedly even though the
weigh bin has filled to overflowing.
2000.0 grams.
*
The weigh bin is not free to move.
*
The load cells are jammed.
*
The load cells are damaged.
The system operates but always needs MANY RETRIES to complete a
dispense and never seems to "learn" the proper dispense rate.
*
Vibration is causing frequent "bailouts" causing large swings in
rate adjustment.
The THUMBWHEEL SWITCHES do not seem to be controlling output.
more LEDs (bottom row) are on all the time.
*
Someone has LOCKED IN a setting using the keypad.
PROGRAM MODE, SETTING.
*
The _SE parameter is LIMITING the thumbwheel switch setting.
KEYPAD, PROGRAM MODE, and PARAMETERS, _SE.

TYPICAL PROBLEMS:

In this case it will most likely be off
See LOAD CELL CALIBRATION.
See CHECKING THE LOAD CELLS
The display says (N
The weight reading is still below
See CHECKING THE LOAD CELLS
Increase the BER parameter.
Page 83
This indicates
After a few seconds the
x.x) and is flashing.
The cylinder mount may be
See KEYPAD,
One or
See