Follow these steps:
1. Obtain root access
2. Login with SSH (use for example Putty in Windows - or simply type ssh root@[ip address here] on
a Linux or Mac terminal console.
3. List the latest log file:
cat /log/dbus-modbustcp/current | tai64nlocal
In case of any errors, the output will look like this:
2016-01-08 16:34:24.658248500
connecion:
"141.138.140.60:41792"
2016-01-08 16:34:24.695846500 ERROR 2016-01-08T16:34:24.689 "Error
processing function code 3, unit id 247, start address 258, quantity 42 :"
"Unit id is available, but start address does not exist"
2016-01-08 16:34:24.753921500
Disconnected:
In most cases the problem will be found in either the unit's id address; or the register addresses.
Double check the numbers shown in the output with the numbers as used in your modbustcp software
or PLC.
Q8: Does Modbus TCP support ESS?
Yes. See the ESS mode 2 and 3 manual for more details.
"141.138.140.60:41792"
INFO 2016-01-08T16:34:24.657 [Server] New
INFO 2016-01-08T16:34:24.753 [Server]