situation. As it will not take the discharge and charge currents by those other DC Loads, and also
unmonitored chargers, into account.
2.2.5 Details on VE.Bus SOC
While the Inverter/Charger is in bulk, the SOC will not rise above the value as set in
VEConfigure3 for the "State of charge when Bulk finished" parameter on the General tab;
default 85%. In a system with Solar chargers, make sure that the Absorption voltage as
configured in the MPPT is slightly above the same setting in the inverter/charger. The latter
needs to recognize that the battery voltage has reached the absorption level. If it doesn't, the
SOC will be stuck at the earlier mentioned End-of-bulk percentage, default 85%.
2.3 Customize the logo on the Boat & Motorhome page
It is possible to use a custom logo onto the Boat & Motorhome page.
Type the following address into the web browser of a device connected to the same network. Using
this address as a template: (inserting your device's IP address between the square brackets). The IP
address can be found by going to Settings > Ethernet or Wifi. Once the page is loaded, Choose an
image file from your device. Re-boot the GX device.
3 VE.Bus Inverter/charger monitoring
3.1 Input current-limiter setting
'Overruled by remote' setting in VEConfigure
This chapter explains the implications of enabling or disabling user control of the input current-limiter
setting, as seen here in the menu: