Color Control GX manual
Thank you for choosing the Color Control Gateway transmitter (CCGX). It sits at the heart of your
energy installation allowing you to view both live and archived data; change settings; instigate
powerful functions; tailor your system to your needs; and to ensure that all the components of your
system are working together, optimally.
All this can be done either with the CCGX in front of you - or from anywhere in the world using an
internet connection, together with the
All the information in this manual refers to the latest software. Your device will update itself to the
latest version automatically. Check our blog posts to see that your device has the latest
firmware:https://www.victronenergy.com/blog/category/firmware-software/
1. Installation
1.1 Overview of connections
Victron Energy - https://www.victronenergy.com/live/
1/27
VictonConnect
application.
Color Control GX manual

Advertisement

loading
Need help?

Need help?

Do you have a question about the CCGX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Victron energy CCGX

  • Page 1 All this can be done either with the CCGX in front of you - or from anywhere in the world using an internet connection, together with the VictonConnect application.
  • Page 2 Last update: 2018-08-21 10:10 ccgx:start https://www.victronenergy.com/live/ccgx:start 1.2 Snap-on ferrite beads for class B EMI compliance In order to reduce Electromagnetic emissions in compliance with class B EMI you should place the provided snap-on ferrite beads around every connection cable as close as possible to the Color Control.
  • Page 3 2018-08-21 11:59 3/27 Color Control GX manual around the power lea HQ1654 and earlier For serial numbers HQ1654 and earlier, mount the snap-on ferrite beads as below: Victron Energy - https://www.victronenergy.com/live/...
  • Page 4 Powering in systems with VE.Bus BMS When the CCGX is used in an installation with a VE.Bus BMS, connect the Power in V+ on the CCGX to the terminal labelled 'Load disconnect' on the VE.Bus BMS. Connect both negative leads to the negative stub of a common Battery.
  • Page 5 (after any operational fault or during a black start). The VE.Bus devices will not boot-up until the CCGX has power …but the CCGX will not boot-up until it has power. This deadlock can be rectified by briefly unplugging the CCGX VE.Bus cable at which point you will observe the VE.Bus products will immediately begin to boot-up.
  • Page 6 CCGX. The jumper link needs to be in the header, as it is by default. Single VE.Bus products To connect a single VE.Bus product, connect it to one of the VE.Bus sockets on the back of the CCGX. Both sockets are identical, use either one. Use a standard RJ45 UTP cable, see our pricelist.
  • Page 7 It is possible to connect both a CCGX and a Digital Multi control to a VE.Bus system. The ability to switch the product On, Off or set it to Charger Only via the CCGX will be disabled. The same applies to...
  • Page 8 Other notes: In order to work with the CCGX an MPPT 150/70 needs run firmware v2.00 or newer. You can combine a Skylla-i control panel with a CCGX. You can combine a Ion Control panel with a CCGX.
  • Page 9 The NMEA2000 function class needs to be 'Transducer', 190 For some tank senders it is also possible to configure the capacity and the fluid type from the CCGX - for example the Maretron TLA100. This facility may be available with other senders made by other manufacturers - it's well-worth trying.
  • Page 10: Internet Connectivity

    Android VRM App. In addition to remote monitoring, an active internet connection allows the CCGX to regularly check for a new firmware versions - which will be automatically downloaded and installed. There are several ways to connect a CCGX to the internet:...
  • Page 11 1.6.3 Mobile (cellular) network using a 3G or 4G router To connect the CCGX to a mobile (cellular) network, such as a 3G or 4G network, use a cellular router. Connect the CCGX to that router with either a LAN cable or the router's Wi-Fi network.
  • Page 12 1.6.6 Connecting both Ethernet and Wi-Fi (failover) It is possible to connect the CCGX to both Ethernet and Wi-Fi. In this case, the CCGX will try to determine which interface provides an active internet connection and then use that interface. When both have an active internet connection, the Ethernet connection is used.
  • Page 13: Configurable Parameters

    Set this to 'User' to prevent accidental and unwanted changes to the configuration. installer Audible alarm On When there is an alarm on the CCGX or a connected product, the CCGX will beep - unless this setting is set to 'Off'. Victron Energy - https://www.victronenergy.com/live/...
  • Page 14 Trouble shooting Remote Console Enable on VRM No on VRM Enabling will allow direct connection to the CCGX by typing it's IP address into a web browser. Only Enable this function Enable on LAN No on trusted networks. System setup AC input 1 Generator Select Generator or Grid.
  • Page 15 Select the relay function. Possible functions are 'Alarm relay', 'Generator start/stop', 'Tank pump' and 'None' (disabled). relay Normally Select the polarity of the relay on the back of the CCGX. 'Normally open' or 'Normally closed'. (Note that setting it to Polarity open normally closed increases the CCGX power draw.)
  • Page 16 2.2 Logging data for the VRM portal The CCGX can be used in combination with the Victron Remote Management (VRM) portal: The CCGX monitors all products connected to it and the VRM portal makes the statistics easily accessible.
  • Page 17 The first step is to use the GUI (Graphical User Interface) to eject the storage (don't just remove the SD-card/USB-stick). The storage device can then be removed from the CCGX and inserted into a computer or laptop, the data file on it can be uploaded on the VRM Portal with the 'Upload CCGX File' option: It's important to know that when the microSD card or USB stick is re-inserted, the existing buffer -...
  • Page 18 If both a microSD card and a USB flash drive are connected to the CCGX, then data is logged to the one that was inserted first. If one is removed, the CCGX will not try to write to the other, but will create an internal backlog buffer until a new storage medium is inserted when it will use that storage...
  • Page 19 19/27 Color Control GX manual The limit as set by the user in the CCGX will be applied to all inputs where 'Overruled by remote', configured with VEConfigure, is enabled: Using the example of a boat with two AC inputs and a Quattro where: A Genset capable of delivering 50A is connected to input 1;...
  • Page 20: Minimum Input Current Limit Values

    Last update: 2018-08-21 10:10 ccgx:start https://www.victronenergy.com/live/ccgx:start Also the on/off/charger only switch in the CCGX will be disabled in the case. In installation with a VE.Bus BMS, use the rocker switch instead - or add a Digital Multi Control to the installation.
  • Page 21 Configuration: Enable and configure the Battery Monitor in VEConfigure. In the CCGX, in Settings → System setup, verify the selected Battery Monitor. It should be set to the Multi or Quattro. Battery with Multi or Quattro and MPPT Solar Chargers -ALSO- An EasySolar with CCGX built-in No battery monitor is required, as long as all MPPT Solar Chargers are Victron products and are connected to the CCGX.
  • Page 22 Connect the battery communications cable to the CCGX according to the instructions. In the CCGX, in Settings → System setup, verify that the selected Battery Monitor is the battery. Note that the Battery Monitor setting in VEConfigure3 is irrelevant. For systems like this, changing this setting will have no effect on the charge or any other parameters in this type of system.
  • Page 23 Multi or Quattro installed no BMV or other battery monitor is installed the system has other DC loads, or other chargers, connected to the same battery, which are not connected to the CCGX. Victron Energy - https://www.victronenergy.com/live/...
  • Page 24: Introduction And Requirements

    For Gel, AGM, OPzS and other lead batteries, DVCC can be used without any problem. The same is true for Victron Energy lithium batteries with the VE.Bus BMS, the Lynx Ion + Shunt BMS or the Lynx Ion BMS. DVCC is the preferred operating mode for Redflow ZBM2/ZCell batteries using the Redflow CANBus BMS.
  • Page 25 When inverting, ie in Island mode, Multis and Quattros will shut down when the max discharge current is zero. They will automatically start again as soon as either AC mains returns, or when BMS increases the max discharge current again. Victron Energy - https://www.victronenergy.com/live/...
  • Page 26: Disqus Comments

    #7: User configured a discharge limit of zero. 4 More information resources CCGX Genset start/stop CCGX Frequently asked questions CCGX Firmware upgrade to v2.00 or later CCGX Manually updating firmware CCGX Remote VEConfigure and remote firmware updates CCGX Datasheet CCGX & Fischer Panda generators...