Fronius / Victron specifics
This is a very easy setup. The Fronius Setup Microgrid has been developed in close cooperation with
Victron. During commissioning, set the PV Inverter to Setup MG50 (or Setup MG60 for 60 Hz systems).
Everything is then pre-configured. The Setup MG settings match the default Victron Assistant settings.
Compatible ROW inverters (for "European type AC grid") are:
Fronius Primo (1~, 3 kW up to 8.2 kW) → Software fro27140.upd or higher (see FAQ Q5!)
Fronius Symo (3~, 3 kW up to 20 kW) → Software fro27140.upd or higher (see FAQ Q5!)
Fronius Eco (3~, 25 kW or 27 kW) → Software fro27140.upd or higher (see FAQ Q5!)
Fronius Agilo (3~, 75 kW up to 100 kW) → Software update19.tl or higher
Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) → from IGF 5.0.66 on with settings according
to the Victron recommendations
For new systems the Fronius Symo and Fronius Eco inverters are recommended for 3~ applications.
The Fronius Primo inverters are recommended for 1~ applications. Please note that all these inverters
are transformerless and therefore PV-Modules that require pole-grounding (on the Plus or Minus pole)
cannot be connected.
The use of Fronius Galvo inverters is not recommended anymore for new applications - the Fronius
Primo is the best substitute and offers higher efficiency, wider DC voltage range and two MPP
trackers.
Compatible UL inverters (for "US type AC grid") are:
Fronius Primo UL (1~, 3.8 kW up to 15 kW) → Software fro27470.upd or higher (see FAQ Q5!)
Fronius Symo 10-24 480V (3~, 10 kW up to 24 kW) → Software fro27140.upd or higher (see FAQ
Q5!)
Fronius Symo 10-15 208-240V (3~, 10 up to 15 kW) → Software fro27140.upd or higher (see
FAQ Q5!)
For the UL inverters, some more Microgrid Setups are available (e.g. for connection with Neutral
conductor or without). Also the UL inverters can be used in 60Hz as well as in 50Hz applications. More
information can be found in the user manuals.
When setting up a system, always update both the Fronius and the Victron devices to their latest
firmware versions. For the latest Fronius firmware and information how to update use this link: Fronius
firmware update
Setting up the Fronius with Setup MG50/MG60
When not pre-ordered with a MicroGrid setup, follow these steps:
1.
Make sure that the Fronius PV inverter is updated to at least the firmware version mentioned
above. See Inverter list above.
2.
After making the inverter operational according to the manual, select the language and after
this the country specific setup.
3.
Here choose MG50 or MG60 depending on the system frequency.