Victron energy Venus GX Manual page 40

Hide thumbs Also See for Venus GX:
Table of Contents

Advertisement

Item
Default
Description
Enabling on VRM will allow connection to the CCGX from anywhere via the VRM portal. Trouble shooting Remote Console
Enable on VRM No
on VRM
Enabling will allow direct connection to the CCGX by typing its IP address or Venus.local into a web browser, or in
Enable on LAN No
VictronConnect when connected to the same network. Only Enable this function on trusted networks. Disable password
check, or set password first
System setup
AC input 1
Generator Select Generator or Grid. (We will shortly be adding the setting 'Shore power' instead of grid.)
AC input 2
Grid
Same choices as above.
Battery
Automatic Select the SOC source. This function is useful where there is more than one BMV. More details.
monitor
Continuously copies the SOC from the battery monitor to the VE.Bus system. This feature is automatically enabled when
Synchronize VE.Bus SOC
the active SOC source is not a VE.Bus device, and there is no Hub-2 Assistant configured. The purpose of this is to be
with battery
able to use the BMV SOC to trigger some Multi or Quattro features - such as Genset start/stop. Multis and Quattro's don't
use the SOC for any other purpose. More information
Send the total charge current from all connected Solar chargers to the VE.Bus device to improve its SOC computations.
Use solar charger current
This feature is automatically active when 'Synchronize VE.Bus SOC with battery' is not active. Requires Multi Firmware
to improve VE.Bus SOC
version >= 402. More information
Use the 'charge voltage' information provided by the VE.Bus device to control the amount of power fed from solar
Solar charger voltage
chargers back to the grid. Active if the ESS or Hub-1 assistant is present. (See also: 'Feed-in excess solar charger power'
control
in the ESS settings.)
Solar charger current
Limit the charge current of the connected solar chargers if a CAN.bus BMS is present - using the maximum charge
control
current information provided by the BMS.
Enable this for boats, vehicles and installations with DC loads and chargers - in addition to Multi and MPPT chargers. This
won't be applicable to most off-grid installations; and any discrepancy between the DC current measured by the Multi,
and by the BMV, will be attributed to a 'DC system'. This may be power-in from an alternator, or power-out from a pump,
for example.
Has DC system No
A positive value indicates consumption. A negative value indicates charging, for example by an alternator.
Note that the value shown will always be an approximation, and is affected by the variation in sample rate between
elements of the system.
Display & language
Brightness
Configure the brightness between 0 and 100%
Display off
Set time-to-off between 10s / 30s - 1m / 10m /30m - or never
time
Enable this to show the mobile overview page which is designed for Marine and Remote Vehicle applications. This
Show mobile
No
overview gives direct access to the AC Current limit as well as the On/Off/Charger-only settings and pump control. Also
overview
shows up to four tank levels.
Language
English
Choose between English, Dutch, Chinese, German, Spanish, French, Italian, Swedish, Turkish and Arabic.
VRM online portal
Set to anything between 1 minute and 1 day. Choose longer times on systems with an unreliable connection. Note that
15
Log interval
this setting does not affect reporting problems and state changes (bulk → absorption) to the VRM Portal. These events
minutes
initiate an immediate transmission of all parameters.
Rest of
See section 5.3, Datalogging to VRM, for more details
parameters
Wireless AC Sensors
Select the position for each AC sensor (PV Inverter on AC-input 1, 2 or on AC-output). More information about the Wireless AC sensors.
Energy meters
Configure the Energy meters, used for one of three things:
Measure the output of a PV Inverter
Measure and regulate a Hub-4 system
Measure and regulate a ESS system
Measure the output of an AC Generator.
ESS
Configure Energy storage system (ESS) ESS system.
Hub-4
Configure Hub-4 system Hub-4 system.
Ethernet
Select the configuration type (DHCP vs. manual configuration) and IP settings.
Wi-Fi
Manage wireless networks and IP settings.
GPS
Format
Select the format in which to show the Latitude and Longitude.
Speed unit
km/h
Choose between km/h, meters per second, miles per hour, or knots.
Generator start/stop
Configure generator autostart settings and conditions. GX - Generator auto start/stop
Tank pump
Configure automatic starting and stopping of pump based on tank level(sender) information. Pump auto start/stop with Color Control GX
Relay
Alarm
Function
Select the relay function. Possible functions are 'Alarm relay', 'Generator start/stop', 'Tank pump' and 'None' (disabled).
relay
Color Control GX manual