Daikin SkyAir RZR-P Series Service Manual page 95

Cooling only / heat pump r-410a 60hz
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

SiUS281117
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
Image of operation in the case of A
Operation sound
Rated operation
sound
Operation sound of
Approx. 55 db (target)
level 1
(The power consumption may be
Operation sound of
increased by about 10 %.)
level 2
Approx. 50 db (target)
(The power consumption may be
Operation sound of
increased by about 20 %.)
level 3
Approx. 45 db (target)
(The power consumption may be
increased by about 30 %.)
Note1: Above values are reference only (measured in silent room)
Note2: Above values are for 1 module only.
Image of operation in the case of B
Operation sound
Time set with "Low night noise start setting"
Rated operation
sound
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
Image of operation in the case of A and B
Operation sound
Time set with "Low night noise start setting"
Rated operation
sound
Operation sound
of level 1
Operation sound
of level 2
Operation sound
Low noise mode instructing
of level 3
Operation sound set with
"External low noise setting"
88
"08:00") for set item No. 27 (Setting of end time of low night noise operation).
(Use the end time as a guide since it is estimated according to outdoor air temperatures.)
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)
If capacity priority is set in "Capacity
priority setting", the fan speed will be
increased according to the load of air
conditioning when load is heavier.
PM 8:00
PM 10:00
PM 0:00
Set with "Low night noise start setting".
(Factory setting is "PM 10:00".)
If capacity priority is set in "Capacity priority
setting", the fan speed will be increased
according to the load of air conditioning
when load is heavier.
Operation sound
level set with "Low
night noise setting"
PM 8:00
PM 10:00
PM 0:00
Set with "Low night noise start setting".
(Factory setting is "PM 10:00".)
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased according
to the load of air conditioning
when load is heavier.
Low noise mode instructing
Operation sound level set with "External low noise setting"
Night-time
Operation sound level set with
"Low night noise setting"
AM 6:00 AM 7:00 AM 8:00
Set with "Low night noise end setting".
(Factory setting is "AM 8:00".)
Time set with "Low night noise end setting"
Night-time
Low noise mode
instructing
Operation sound set with
"External low noise setting"
AM 6:00 AM 7:00 AM 8:00
Set with "Low night noise end setting".
(Factory setting is "AM 8:00".)
Field Setting from Outdoor Unit
Operation sound during low
noise mode is instructed
can be set with "External low
noise level setting"
(Factory setting is "Mode 2".)
Time set with "Low night noise end setting"
Operation sound during
night-time low noise mode is
instructed can be set with
"Low night noise level
setting".
(Factory setting is "OFF".)
Operation sound during low noise
mode is instructed can be set with
"External low noise level setting".
(Factory setting is "Mode 2".)
Operation sound during low night
noise mode is instructed can be
set with "Low night noise level
setting".
(Factory setting is "OFF".)
When external low noise
instruction is received during the
operation with low night noise
mode.
Mole 2 precedes Level 1 and
Level 3 precedes Level 2.
Field Setting