Setting Mode 2 - Daikin SkyAir RZR-P Series Service Manual

Cooling only / heat pump r-410a 60hz
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

SiUS281117
3.5

Setting Mode 2

Press and hold the MODE button
(BS1) for 5 seconds and set to

"Setting mode 2".

<Selection of setting items>
Press the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
Press the RETURN button (BS3)
and decide the item. (The present
setting condition is blinked.)
<Selection of setting conditions>
Press the SET button (BS2) and set
to the setting condition you want.
Press the RETURN button (BS3)
and decide the condition.
Press the RETURN button (BS3)
and set to the initial status of
"Setting mode 2".
∗ If you become unsure of how to
proceed, press the MODE button
(BS1) and return to setting mode 1.
84
No.
Setting item
Indoor unit forced
Allows forced operation of indoor unit fan while unit is
5
fan H
stopped. (H tap)
Indoor unit forced
6
Allows forced operation of indoor unit.
operation
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
Defrost changeover
Changes the temperature condition for defrost and sets to
10
setting
quick defrost or slow defrost.
External low noise
12
setting / Demand
Reception of external low noise or demand signal
setting
16 Setting of hot water
Make this setting to conduct heating operation with hot
heater
water heater.
Refrigerant
recovery /
21
Sets to refrigerant recovery / vacuuming mode.
vacuuming mode
setting
Sets automatic low night noise operation in a simple way.
Low night noise
22
The operating time is based on "Starting set" and "Ending
operation setting
set".
Low night noise
Sets starting time of low night noise operation. (Low night
26
operation start
noise operation setting is also required.)
setting
Low night noise
Sets ending time of low night noise operation.
27
operation
(Low night noise setting is also required.)
end setting
If the capacity control is required, the low noise control is
Capacity priority
29
automatically released by this setting during carrying out
setting
low noise operation and nighttime low noise operation.
Changes target value of power consumption when
30 Demand setting 1
demand control 1 is input.
Normally enables demand control 1 without external
Normal demand
32
input. (Effective to prevent a problem that circuit breaker
setting
of small capacity is shut down due to large load.
Field Setting from Outdoor Unit