SiUS281117
2.27 Electronic Expansion Valve Coil Abnormality
E9
Remote
Controller
Display
Applicable
RZR, RZQ
Models
Method of Error
Detect errors based on check of continuity of the electronic expansion valve.
Detection
Detect errors by suction pipe superheated degree, discharge pipe superheated degree and
electronic expansion valve opening degree.
No common power supply when the power is turned ON
Error Decision
When the following conditions are established
Conditions
Defective electronic expansion valve
Supposed
Disconnection of electronic expansion valve harness
Causes
Defective connection of electronic expansion valve connector
Defective each thermistor
Defective of each thermistor mounting
Defective pressure sensor
Defective outdoor unit control PCB
Wet operation
138
Suction pipe superheated degree 39.2°F
Discharge pipe superheated degree 41°F
Electronic expansion valve opening degree Minimum opening degree
Troubleshooting by Remote Controller
Service Diagnosis