Troubleshooting by Remote Controller
2.39 Inverter Startup Error
L9
Remote
Controller
Display
Applicable
RZR, RZQ
Models
Method of Error
The error is detected from the current flowing to power transistor into voltage with CT1 (DC
Detection
current sensor).
Inverter PCB detects the disorder of position signal.
Error Decision
When compressor overload (when startup) is detected
Conditions
The stop valve is not opened.
Supposed
Pressure differential startup
Causes
Defective outdoor unit inverter PCB
Defective compressor (lock)
Service Diagnosis
SiUS281117
157