SiUS281117
Symptom
11 The system
<Indoor unit>
produces
Immediately after turning ON
sounds.
the power supply, indoor unit
produces "ringing" sounds.
<Indoor and outdoor units>
"Hissing" sounds are
continuously produced while in
cooling or defrosting operation.
<Indoor and outdoor units>
"Hissing" sounds are produced
immediately after the startup or
stop of the system, or the
startup or stop of defrosting
operation.
<Indoor unit>
Faint sounds are continuously
produced while in cooling
operation or after stopping the
operation.
<Indoor unit>
"Creaking" sounds are
produced while in heating
operation or after stopping the
operation.
<Outdoor unit>
Pitch of operating sounds
changes.
12 Dust comes out
Dust comes out from the
from the system.
system when it restarts after
the stop for an extended period
of time.
13 Odors come out
In operation
from the system.
14 Outdoor unit fan
In operation
does not rotate.
88
15 LCD display "
"
Immediately after turning ON
appears on the
the power supply
remote
controller.
16 The outdoor unit
After stopping operation
compressor or
the outdoor unit
fan does not
stop.
17 The outdoor unit
While stopping operation
gets hot.
18 The system does
The system is in dry operation. The reason is that the dry
not cool air well.
98
Supposed Cause
These are operating sounds of
the electronic expansion valve of
the indoor unit.
These sounds are produced from
gas (refrigerant) flowing
respectively through the indoor
and outdoor units.
These sounds are produced
when the gas (refrigerant) stops
or changes flowing.
These sounds are produced from
the drain discharge device in
operation.
These sounds are produced from
resin parts expanding and
contracting with temperature
changes.
The reason is that the compressor
changes the operating frequency.
Dust, which has deposited on the
inside of indoor unit, is blown out
from the system.
Odors of room, cigarettes or else
adsorbed to the inside of indoor
unit are blown out.
The reason is that fan revolutions
are controlled to put the operation
to the optimum state.
The reason is that the system is
checking to be sure the remote
controller is normal.
It stops in order to prevent oil or
refrigerant from dwelling.
The reason is that the compressor
is warmed up to provide smooth
startup of the system.
operation serves not to reduce
the room temperature where
possible.
Symptom-based Troubleshooting
Countermeasure
Normal operation.
This sound becomes low after a
lapse of approximately 1 minute.
Normal operation.
Normal operation.
Normal operation.
Normal operation.
Normal operation.
Normal operation.
The inside of the indoor unit
should be cleaned.
Normal operation.
Normal operation.
This code is displayed for a period
of approximately 1 minute at
maximum.
Normal operation.
It stops after a lapse of
approximately 5 to 10 minutes.
Normal operation.
Change the system to cooling
operation.
Service Diagnosis