Daikin SkyAir RZR-P Series Service Manual page 85

Cooling only / heat pump r-410a 60hz
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

SiUS281117
2.3.3 Setting of Operation Control Mode from Remote Controller
(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information in the next page.)
The centralized controller is normally available for operations, except when the centralized
monitor is connected.
2.3.4 Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
 ON/OFF control impossible by remote controller
 OFF control only possible by remote controller
 Centralized
 Individual
 Timer operation possible by remote controller
78
Used when you want to turn ON/OFF by centralized remote controller only.
(Cannot be turned ON/OFF by remote controller.)
Used when you want to turn ON by centralized remote controller only, and OFF by remote
controller only.
Used when you want to turn ON by centralized remote controller only, and turn ON/OFF
freely by remote controller during set time.
Used when you want to turn ON/OFF by both centralized remote controller and remote
controller.
Used when you want to turn ON/OFF by remote controller during set time and you do not
want to start operation by centralized remote controller when time of system start is
programmed.
Field Setting from Remote Controller
Field Setting