Commissioning
4.6 Extended Safety
●
●
4.6.1.2
Configuring activation via FDI
● Click the "Drive" button.
●
122
②
If you use one of the safety functions SS1 or SLS, then you must select the monitoring
mode of these functions.
More detailed information on the modes can be found in the following sections:
– Monitoring modes of SS1 (Page 21)
– Monitoring modes of SLS (Page 28)
③
Click on the button for configuring the fail-safe inputs and outputs.
①
In the following screen form, you assign the fail-safe inputs to the safety functions.
If you do not want to use a particular safety function, set the relevant input to "(255)
Statically inactive".
Safety Integrated Function Manual, SINAMICS G120 and G120C