4.5.2.2
Setting STO
● Define the time interval for forced dormant error detection and connect the appropriate
Information on forced dormant error detection can be found in the section Forced dormant
error detection (test stop) (Page 72).
4.5.2.3
Activate settings
● Click "Copy parameters" and then click "Activate settings":
● You are prompted to allocate a password if the password = 0 (factory setting).
● Confirm the prompt for saving your settings (copy RAM to ROM).
● Switch off the inverter supply voltage.
● Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
message to any signal:
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 71).
again. Your settings only become effective after this power-on reset.
Commissioning
4.5 Basic Safety
115