Commissioning
4.6 Extended Safety
4.6.2.10

Setting SDI

The principle of operation of SDI is provided in section Safe Direction (SDI) (Page 42).
● Set the following in this screen form:
4.6.2.11

Defining the F-DI status

If you do not want to transfer the status of the fail-safe inputs via PROFIsafe, go straight to
the section Activate settings (Page 145).
If you want to transfer the status of the fail-safe digital inputs via PROFIsafe, you first have to
configure the relevant PROFIsafe telegram; see the section Configuring communication in
STEP 7 (telegram 900) (Page 102). In STARTER, you then have to specify which F-DI-
Status you want to transfer via PROFIsafe.
144
Enable the function
Delay time between selecting SDI and the active SDI:
The delay time must be greater than the time that the motor requires, when SDI is
selected, for braking with the maximum load from the maximum speed down to
standstill.
Tolerance for the permissible motion in the monitored direction (Unit: degree)
Reaction when the monitoring responds
See also section: STOP reactions (Page 192)
Behavior when the motor is switched off
Also see section: Switching off the motor when SDI is active (Page 44)
⑥ ⑦
If you interconnect the monitoring with speed limits p1051 and p1052, the
inverter limits the speed when SDI is active.
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB