Setting Sto - Siemens SINAMICS G120 Function Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

4.6.2.6

Setting STO

● Configure the following settings in this screen form:
● Close the screen form.
● If you do not use any other safety function, go directly to Section Activate settings
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
Forced dormant error detection of the switch-off signal paths
You define the monitoring of the forced checking procedure in another screen form
(Forced dormant error detection (test stop) (Page 72)). Set this time to the maximum
value (9000 hours).
If you need this signal in your control, connect it to any digital output of your choice
or to a status word on the fieldbus.
Setting is not required
(Page 145).
Commissioning
4.6 Extended Safety
139

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c

Table of Contents