Settings In Twincat; Fig. 10 Representation Of The El9930 In Twincat - Beckhoff EL9930 Operating Instructions Manual

Profisafe segment end terminal
Hide thumbs Also See for EL9930:
Table of Contents

Advertisement

Operation
4.2.5

Settings in TwinCAT

Scan or create the IO configuration
Each EL9930 registers itself twice in the configuration in TwinCAT:
• once as EL9930-0000 (primary, shown in figure as EL9930)
• once as EL9930-0001 (secondary).
The reason for this is that both the forward and backward direction of the EtherCAT telegram have to be
regarded for the ending of the PROFIsafe segment on account of the functional principle of EtherCAT. The
representation EL9930-0001 (secondary) is a virtual node in the I/O configuration (no real component). Both
instances must be placed correctly so that the PROFIsafe segment is limited in accordance with the
PROFIsafe policy (see illustration below). The primary and secondary instance must be at the same level in
the I/O tree, while the elements between these instances must be configured as a subtree of the primary
instance.
By using the scan function in TwinCAT 3, you can ensure that the integration of the two instances of each
EL9930 in the I/O tree is executed correctly.
Fig. 10: Representation of the EL9930 in TwinCAT
Alias Device
To connect the EL6910 with a PROFIsafe device, a corresponding Alias Device must be created and the
desired telegram length configured.