UPS2000-G-6KRTLL
User Manual
4.6 Alarm Handling
Table 4-10 Alarm handling
Alarm ID
Alarm
Name
01
Fan blocked
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Minor
The fan
automatical
ly recovers
from
blockage.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The fan
The current
blockage
working
signal is at
status is
low level
not
for 15s
affected. If
within 30s.
overtemper
ature
protection
is triggered,
the system
may
transfer to
bypass
mode.
4 Control Panel
Suggestion
● Possible
cause:
The fan
is
blocked.
Measure:
Check the
fan and
remove
sundries.
● Possible
cause:
The fan
is faulty.
Measure:
Replace the
fan.
63