Huawei UPS2000-G-6KRTLL User Manual page 91

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

UPS2000-G-6KRTLL
User Manual
Alarm ID
Alarm
Name
51
Output
overcurrent
52
Bus
undervoltag
e
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The output
The system
current
shuts down
exceeds 80
the inverter
A for 1 ms.
and
transfers to
bypass
mode.
● Battery
The system
mode:
shuts down
The bus
the inverter
voltage
and
is less
transfers to
than 7
bypass
times
mode.
the
battery
voltage
by over
100 V.
● Normal
mode:
The bus
voltage
is less
than the
peak
mains
voltage
by over
80 V.
4 Control Panel
Suggestion
● Possible
cause:
The
transient
load
power is
too high.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
● Possible
cause:
The
transient
load
power is
too high.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
85