Alarm ID
Alarm
Name
53
Timeout in
approachin
g rated
output
voltage
during
startup
55
Excessive
DC
component
57
Current
sensor fault
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Critical
The alarm
can be
automatical
ly cleared
for three
times. After
that, you
need to
manually
clear the
fault or
power off
and restart
the device.
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The inverter
The system
voltage is
shuts down
not soft-
the inverter
started to
and
the rated
transfers to
output
bypass
voltage
mode.
within 10s.
The DC
The system
component
shuts down
of the
the inverter
output
and
voltage is
transfers to
greater
bypass
than 200
mode.
mV for 20s.
In power-on
The system
mode, the
cannot start
current
the inverter
sampling
and directly
deviation
delivers
exceeds
output in
10% of the
bypass
total
mode.
sampling
range.
4 Control Panel
Suggestion
Possible
cause: The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
● Possible
cause:
The half-
wave
load
power is
too high.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
Possible
cause: The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
86