Alarm ID
Alarm
Name
82
Parallel
synchroniza
tion signal
fault
83
Parallel
battery
voltage
deviation
exceeding 4
V
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Critical
The voltage
difference is
less than 3
V or the
UPS is set
to
standalone
mode.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The
The system
synchroniza
shuts down
tion zero-
the inverter
crossing
and
signal is
transfers to
lost for
bypass
more than
mode. If
200 ms.
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
The battery
The system
voltage
shuts down
deviation
the inverter
between
and
UPSs in a
transfers to
parallel
bypass
system is
mode. If
greater
other UPSs
than 4 V for
in the
120 ms.
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
4 Control Panel
Suggestion
Possible
cause: The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
Possible
cause:
Batteries
are not
shared.
Measure:
Ensure that
all UPSs
share one
battery
string.
91