UPS2000-G-6KRTLL
User Manual
Alarm ID
Alarm
Name
58
Low output
voltage
59
Charger
circuit
overcurrent
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The output
The system
voltage is
shuts down
lower than
the inverter
the rated
and
voltage by
transfers to
50 V for 3s.
bypass
mode.
The charge
The system
current is
shuts down
greater
the inverter
than 105 A.
and
transfers to
bypass
mode.
4 Control Panel
Suggestion
● Possible
cause:
The
transient
load
power is
too high.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
Possible
cause:
Power grid
surge
occurs.
Measure:
Improve the
power grid
quality.
Possible
cause: The
charger
circuit is
damaged.
Measure:
Replace the
charger
circuit.
87