UPS2000-G-6KRTLL
User Manual
Alarm ID
Alarm
Name
28
The battery
discharge
time
reaches the
maximum.
31
UPS
working in
bypass
mode
32
UPS locked
in bypass
state
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Minor
Set item 05
battery
discharge
time to 0 or
restart the
inverter.
Minor
The UPS
recovers the
inverter
output.
Minor
The inverter
switch is
turned on
again.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The battery
The system
discharge
cannot
time
supply
reaches the
power in
preset
battery
value.
mode. If
this alarm
is
generated
in battery
mode, the
power
output will
be
disconnecte
d.
The UPS
The bypass
works in
power
bypass
output
mode.
alarm does
not affect
the system
working
status. The
power
supply will
be
disconnecte
d if the
bypass
input is
abnormal.
The UPS
The system
transfers to
cannot
bypass
automatical
mode more
ly switch
than three
back to
times
inverter
within 30
mode.
minutes
due to
overload.
4 Control Panel
Suggestion
Check
whether
the mains
input is
normal.
● Check
whether
the UPS
transfers
to
bypass
mode
due to
overload.
● Check
whether
the
inverter
switch is
turned
on.
Possible
cause: The
UPS is
overloaded.
76