UPS2000-G-6KRTLL
User Manual
Name
Battery capacity
Output frequency
Operating mode
Issue 02 (2022-06-30)
Display
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Description
● Default value: 100
Ah
● Value range: 50–
2400 Ah. The value
is incremented by 50
Ah each time you
press SELECT.
● Battery string
sharing enabled:
When setting the
battery capacity, set
the total battery
string capacity for
each UPS.
● Battery string
sharing disabled:
When setting the
battery capacity, set
the capacity of the
battery string
connected to each
UPS.
● 50 Hz (default)
● 60 Hz
Normal mode (default):
When the mains is
available, the UPS
works in normal mode.
If the mains frequency
is unstable, the UPS
works in inverter mode.
Auto mode: When the
mains is available, the
UPS works in normal
mode. If the mains
frequency is unstable,
the UPS works in
bypass mode.
50