Alarm ID
Alarm
Name
60
Load
backfeed
detected
71
Inconsistent
parallel
versions
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
When UPSs
The system
are
shuts down
connected
the inverter
in parallel,
and
the output
transfers to
backfeed
bypass
power
mode. If
exceeds
other UPSs
1200 W for
in the
100 ms.
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
Parallel UPS
If the
protocols
versions are
are
inconsistent
inconsistent
, the non-
.
master UPS
exits the
parallel
system.
Otherwise,
the UPS
transfers to
bypass
mode
because the
number of
parallel
UPSs is
inconsistent
.
4 Control Panel
Suggestion
Possible
cause: Load
backfeed
occurs.
Measure:
Disconnect
the load
and restart
the device.
Possible
cause: The
UPS
software
versions are
inconsistent
.
Measure:
Upgrade
the
software to
the same
version.