Alarm ID
Alarm
Name
06
High output
voltage
07
Download
timeout
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The output
The system
voltage
shuts down
exceeds the
the inverter
rated
and
voltage by
transfers to
20 V for 3s.
bypass
mode.
The output
The system
overload
disconnects
time
the power
exceeds the
output.
specificatio
n.
4 Control Panel
Suggestion
● Possible
cause:
Load
energy
backfeed
occurs.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
Possible
cause: The
load
exceeds the
UPS
capacity.
Measure:
Reduce the
load.