UPS2000-G-6KRTLL
User Manual
Alarm ID
Alarm
Name
03
High
battery
voltage
Issue 02 (2022-06-30)
Severity
Clearance
Condition
Critical
The alarm
is
automatical
ly cleared
when the
battery
voltage is
lower than
58 V.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on
Condition
the System
The battery
The system
voltage is
shuts down
greater
the inverter
than 60 V
and
for 3s.
transfers to
bypass
mode.
4 Control Panel
Suggestion
● Possible
cause:
The
battery
is faulty.
Measure:
Replace the
battery or
discharge
the battery
to a normal
voltage.
● Possible
cause:
The
sampling
is faulty
due to
environ
mental
factors.
Measure:
Send the
device to
the
maintenanc
e center.
65