Starting inverter
7.4
Perform startup operations: On the standby screen, hold down
Release the button when you hear a beep sound. The startup screen is displayed. After the UPS
starts successfully, it enters normal mode. After the system runs properly, close the UPS
downstream AC output switch to start loads.
8

Shutting down the UPS

Shutting down the Inverter to Transfer a Single UPS to Bypass Mode
1
8.1
Perform "shutdown operations" to shut down the UPS. On the default screen, hold down ESC for
more than 5 seconds. Release the button when you hear a beep tone. The inverter shuts down. If
the bypass voltage is within the configured range, the UPS transfers to bypass mode. If the bypass
voltage is beyond the configured range, the UPS has no output.
Powering Off a Single UPS
8.2
1. Shut down loads.
2. Perform "shutdown operations" on the UPS. The inverter shuts down, and the UPS transfers to
bypass mode. If the bypass voltage is beyond the configured range, the UPS has no output.
3. Open the upstream AC input circuit breaker for the UPS based on site requirements, the UPS
downstream AC output switch.
4. Press and hold the MANUAL ON/OFF button on each lithium battery for at least 5s and less than
15s to power off the lithium battery. After all indicators turn off and fans stop, the UPS shuts
down and loads power off.
9

Alarm Handling

Alarm
Alarm ID
Name
(Alarm
ID-Alarm
Cause)
Abnormal
0001-01
mains
volt.
0001-02
0001-03
Abnormal
0010-01
BPS volt.
0010-02
Alarm
Alarm
Impact on the
Severi-
Clear
System
ty
Mode
Minor
Automat
ic clear
Minor
Minor
Minor
Automat
The UPS cannot
ic clear
transfer to bypass
mode. If the bypass is
supplying power, the
Minor
UPS changes the
working mode.
Repair Proposal
The UPS transfers
Possible causes:
to battery mode.
If no battery is
equipped, the
UPS shuts down.
The UPS changes
Measures:
the working mode
or shuts down.
Possible causes:
Measures:
12
for more than 5 seconds.
The mains voltage exceeds 144 V.
The mains voltage is less than 73 V.
The mains frequency is not in the
range of 40 Hz to 70 Hz.
Check whether the mains input voltage
is less than 139 V. If not, wait until the
mains recovers.
Check whether the mains input voltage
is greater than 80 V. If not, wait until
the mains recovers.
Check the mains input frequency. If the
mains input frequency is abnormal,
wait until the mains input recovers.
The bypass input voltage is abnormal.
The bypass input frequency is
abnormal.
Check whether the bypass input
voltage exceeds the configured range.
If yes, change the range or wait until
the bypass input recovers.
Check whether the bypass input
frequency exceeds the configured
range. If yes, change the range or wait
until the bypass input recovers.