2.7 Optional Components

The UPS provides a variety of optional components to address various customer
requirements.
Table 2-8 Optional components
Optional Component
BCB-BOX
Battery bus bar box
(BBB box)
Antiseismic kit
Dry contact card
Short-distance battery
temperature sensor
Ambient T/H sensor
Parallel cable
BSC cable
Issue 15 (2022-11-15)
Model
● PDU8000-0250DCV8-BXA006
● PDU8000-0400DCV8-BXA007
● PDC-0630DC0384BXA
● PDU8000-0063DCV8-BXA002
● PDU8000-0125DCV8-BXA001
● PDU8000-0250DCV8-BXA001
● PDU8000-0400DCV8-BXA001
● PDU8000-0630DCV8-BXA001
● PDU8000-0800DCV8-BXA001
● PDU8000-0630DCV8-BGA001
● PDU8000-1250DCV8-BGA001
● PDU8000-2000DCV8-BGA001
-
RMS-RELAY01A
-
-
5 m/10 m/15 m
15 m
NO TE
Antiseismic kits can be installed only for 60 kVA/80 kVA/120 kVA UPSs.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Product Overview
Function
● Controls the connection
between battery strings and
the UPS.
● Supports overload
protection, short-circuit
protection, and remote trip
management.
Converges the currents of
multiple battery strings.
Reinforces the cabinet so that
the cabinet can resist intensity
9 earthquakes.
Provides output dry contacts.
Monitors the temperature
within 10 m of batteries
indoors.
Monitors ambient temperature
and humidity.
Connects UPSs in a parallel
system.
Transmits bus synchronization
signals in a dual-bus system.
50