Drive Power Enabled Switch, Safety Mode - VAT 613 Series Installation, Operating, & Maintenance Instructions

Butterfly pressure control valve with profibus interface vat2 profile, dn 25-320 mm, i.d. 1“ - 12", 2 sensor inputs / analog outputs / +-15v sps / pfo
Table of Contents

Advertisement

4.5.4

Drive Power Enabled Switch, Safety Mode

28/129
By means of an external switch the motor power supply can be interrupted.
In this case the valve enters the 'safety mode'.
This motor interlock prevents the valve from moving (e.g. maintenance work).
Data reading from the control unit remains possible.
When motor interlock is active during power up, the valve directly enters the 'safety mode'
and is not able to do homing.
When 'safety mode' is entered from operation (i.e. pressure control mode), the unit will
automatically switch to safety control mode and remain at current position.
Once motor interlock is deactivated the valve go to control mode 'Init', so a homing is
necessary and will carried out depending on 'Homing' setting (Refer to 'Power Up, Homing')
For safety function without human risk it is recommend using interlock function of
the digital inputs, because no new homing is necessary after release of the
interlock.
Refer to 'Power connector IO' >> 'Digital Input'
Edition 11.08.2022
INSTALLATION
Series 613
1087976EB