UPS5000-H-600 kVA-FTN
Quick Guide (Singapore, 100 kVA Power Modules)
Step 2 Set Module cycle hiber period(d) to an integer ranging from 1 to 100. The
default value is 30.
Figure 2-7 System settings
Step 3 After the setting is complete, check the status.
Issue 01 (2022-11-18)
NO TE
Click Submit after setting parameters on the WebUI.
LCD: Inverter hibernation is displayed on the System Info. screen. Tap the
UPS picture to display the Cabinet N Data screen. You can select a module
that is hibernating to view its running data.
Figure 2-8 Inverter hibernation
WebUI: Inverter hibernation is displayed on the home page. You can choose
Monitoring > Module Summary > Module N > Running Information to
view the running data of the module.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Single UPS Commissioning
68