UPS5000-H-600 kVA-FTN
Quick Guide (Singapore, 100 kVA Power Modules)
Each ambient T/H sensor has a unique DIP switch address, ranging from 32 to 44.
A DIP switch has six binary toggle switches. The bit on the leftmost is the most
significant bit, and the bit on the rightmost is the least significant bit. Bit 1
indicates ON, and bit 0 indicates OFF.
Table 2-1 DIP switch address mapping
No.
6
5
4
3
2
1
When an ambient T/H sensor is used as a battery temperature sensor, set the DIP
switch to a value in the range of 16 to 28 to monitor the battery temperature.
Table 2-2 DIP switch address mapping (battery temperature sensor)
No
.
6
5
4
3
2
1
Step 2 Set UI parameters.
The address set on the software must be the same as the address set on the DIP
switch. Otherwise, the communication fails.
Issue 01 (2022-11-18)
DIP switch settings on ambient T/H sensors
RS485 Address
32
33
34
1
1
1
0
0
0
0
0
0
0
0
0
0
0
1
0
1
0
DIP switch settings on battery temperature sensors
RS485 Address
16
17
18
19
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
1
1
0
1
0
1
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
35
36
37
38
1
1
1
1
0
0
0
0
0
0
0
0
0
1
1
1
1
0
0
1
1
0
1
0
20
21
22
0
0
0
1
1
1
0
0
0
1
1
1
0
0
1
0
1
0
2 Single UPS Commissioning
39
40
41
42
1
1
1
1
0
0
0
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
23
24
25
26
0
0
0
0
1
1
1
1
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
43
44
1
1
0
0
1
1
0
1
1
0
1
0
27
28
0
0
1
1
1
1
0
1
1
0
1
0
64

Advertisement

Table of Contents
loading

Table of Contents