Pulse Flowmeter Setup; Ramps - Grundfos TPE 1000 Series Installation And Operating Instructions Manual

Table of Contents

Advertisement

"Detection delay"
You can set a detection delay which ensures that the
monitored parameter stays above or below a set limit
in a set time before the function is activated.
"Resetting delay"
The resetting delay is the time from which the
measured parameter differs from the set limit
including the set hysteresis band and until the
function is reset.
Example
The function is to monitor the outlet pressure of a
pump. If the pressure is below 5 bar for more than 5
seconds, a warning must be given. If the outlet
pressure is above 7 bar for more than 8 seconds, you
must reset the warning.
1
2
4
4
A
5
"Limit exceeded" (example)
Pos. Setting parameter
1
Measured
2
"Limit"
3
"Hysteresis band"
4
"Limit exceeded when"
5
"Detection delay"
6
"Resetting delay"
Limit-exceeded function
A
active
-
"Action"
Factory setting
See section Factory settings.
Related information
13.12 "Signal relays 1 and 2" (Relay outputs)
30. Factory settings
3
T[s]
6
Setting
"Outlet pressure"
5 bar
2 bar
"Below limit"
5 seconds
8 seconds
-
"Warning"

13.18 "Pulse flowmeter setup"

Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can connect an external pulse flowmeter to one
of the digital inputs in order to register the actual and
accumulated flows. Based on this, you can also
calculate the specific energy.
To enable a pulse flowmeter, set one of the digital-
input functions to Accumulated flow and set the
pumped volume per pulse. See section "Digital
inputs".
Factory setting
See section Factory settings.
Related information
13.10 Digital inputs
30. Factory settings

13.19 "Ramps"

Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The ramps determine how quickly the motor can
accelerate and decelerate, respectively, during start-
stop or setpoint changes.
You can set the following:
acceleration time, 0.1 to 300 seconds
deceleration time, 0.1 to 300 seconds.
The times apply to the acceleration from 0 rpm to
fixed maximum speed and the deceleration from fixed
maximum speed to 0 rpm.
At short deceleration times, the deceleration of the
motor may depend on load and inertia as there is no
possibility of actively braking the motor.
If the power supply is switched off, the deceleration of
the motor only depends on load and inertia.
"Pulse flowmeter
setup"
"Ramps"
53

Advertisement

Table of Contents
loading

Table of Contents