If two pumps in the system are configured with an
outlet-pressure sensor, both pumps can function as
master pumps and take over the master pump
function if the other fails. This provides additional
redundancy in the multipump system.
The multipump functions are described in the
following sections.
13.43.1 Alternating operation
Alternating operation functions as a duty/standby
operating mode and is possible with two pumps of
same size and type connected in parallel. The main
purpose of the function is to ensure an even amount
of running hours and to ensure that the standby pump
takes over if the running pump stops due to an alarm.
Each pump requires a non-return valve in series with
the pump.
You can choose between two alternating operation
modes:
"Alternating operation, time"
Pump changeover to the other is based on time.
"Alternating operation, energy"
Pump changeover to the other is based on energy
consumption.
If the duty pump fails, the other pump takes over
automatically.
13.43.2 Backup operation
Backup operation is possible with two pumps of same
size and type connected in parallel. Each pump
requires a non-return valve in series with the pump.
One pump is operating continuously. The backup
pump is operated for a short time each day to prevent
seizing up. If the duty pump stops due to a fault, the
backup pump starts automatically.
13.43.3 Cascade operation
Cascade operation ensures that the pump
performance is automatically adapted to the
consumption by switching pumps on or off. The
system thus runs as energy-efficiently as possible
with a constant pressure and a limited number of
pumps.
All pumps in operation run at equal speed. Pump
changeover is automatic and depends on energy,
operating hours and fault.
If the pump system consists of two to four single-head
pumps connected in parallel, the pumps must be of
the same type and size. Each pump requires a non-
return valve in series with the pump.
Set the control mode to "Constant pressure" or
"Constant curve".
This function is available with up to 4 motors installed
in parallel. The motors must be of the same size and
the pumps must be of the same model.
The performance is adjusted to the demand
through cutting pumps in or out and through
parallel control of the pumps in operation.
60
The controller maintains a constant pressure
through continuous adjustment of the speed of the
pumps.
Pump changeover is automatic and depends on
load, operating hours and fault detection.
All pumps in operation run at the same speed.
The number of pumps in operation also depends
on the energy consumption of the pumps. If only
one pump is required, two pumps will run at a
lower speed if this results in a lower energy
consumption.
If several motors in the system have a sensor,
they can all function as master and take over the
master function if the other motors fail.
13.43.4 Setting a multipump system
You can set a multipump system in the following
ways:
Grundofos GO and wireless pump connection
Groundfos GO and wired pump connection
Advanced control panel and wireless pump
connection
Advanced control panel and wired pump
connection
See step-by-step descriptions below.
Grundfos GO and wireless pump connection
1. Power on both pumps.
2. Establish contact to one of the pumps with
Grundfos GO.
3. Set the needed analog and digital inputs via
Grundfos GO according to the connected
equipment and the required functionality. See
section "Assisted pump setup".
4. Assign a pump name to the pump using Grundfos
GO. See section "Pump name".
5. Disconnect Grundfos GO from the pump.
6. Establish contact to the other pump.
7. Set the needed analog and digital inputs via
Grundfos GO according to the connected
equipment and the required functionality. See
section "Assisted pump setup".
8. Assign a pump name to the pump using Grundfos
GO. See section "Pump name".
9. Select the "Assist" menu and "Multipump setup".
10. Select the desired multipump function. See
sections Alternating operation, Backup
operation and Cascade operation.
11. Press [>] to continue.