IT mains ....... . 8 The symbols and hazard statements below may appear in Grundfos installation and operating instructions, safety instructions and Aggressive environment .
Technical documentation is available on Grundfos Product Center Minor or moderate personal injury at www.grundfos.com. ‐ Use proper lifting equipment when handling the prod- If you have any questions, please contact the nearest Grundfos uct. company or service workshop. ‐ Follow local regulations.
4. Installation requirements Any installation, maintenance and inspection must be car- ried out by trained persons. WARNING Sharp element Death or serious personal injury ‐ Use safety knives and protective gloves when unpack- ing the product. WARNING Heavy lifting Death or serious personal injury ‐...
4.1 IT mains 5. Mechanical installation The individual CUE cabinet sizes are characterised by their Do not connect 380-500 V CUE frequency converters to enclosures. The table in section Enclosure shows the relationship mains supplies with a voltage between phase and protec- between enclosure class and enclosure type.
CUE and the supply system must be protected against short circuit. cable with screen connected to CUE (controller with no cable Grundfos requires that the backup fuses mentioned in section clamps). Cable cross-section to signal terminals are used for protection •...
Example of connection of a 3-conductor bus cable with screen connected at both ends Pos. Description Wiring diagram, three-phase mains connection Controller Terminal Function (L1) (L2) Three-phase mains supply (L3) 95/99 (PE) Protective earth connection Three-phase motor connection, 0-100 % of mains voltage Example of connection of a 3-conductor bus cable with screen connected to CUE (controller with no cable clamps)
6.4.4 Motor connection, enclosures B2 6.5 STO installation, optional 1. Connect the earth conductor to terminal 99 (PE). See the figure DANGER below. Exposure to high pressure or toxic liquids 2. Connect the motor conductors to terminals 96 (U), 97 (V), 98 Death or serious personal injury (W).
6.5.1 Restart behaviour after STO activation By default the STO function is set to unintended-restart prevention behaviour. To terminate STO and resume normal operation with manual reset, do the following: • Reapply 24 V DC supply to terminal 37. • Send a reset signal via bus, Digital I/O or the reset button.
Page 15
Terminal Type Function Terminal Type Function +24 V out Supply to sensor Frame for analog output +24 V out Additional supply AO 1 Analog output, 0-20 mA DI 1 Digital input, programmable +10 V out Supply to potentiometer DI 2 Digital input, programmable AI 1 External setpoint, 0-10 V, 0/4-20 mA...
RS-485 GENIbus network connection 6.7 Connecting the signal relays One or more CUE units can be connected to a control unit via As a precaution, signal cables must be separated from GENIbus. other groups by reinforced insulation in their entire The reference potential, GND, for RS-485 (Y) communication must lengths.
Page 17
Configuration of MCB 114 MCB 114 is equipped with three analog inputs for the following sensors: • One additional sensor 0/4-20 mA. • Two Pt100/Pt1000 temperature sensors for measurement of motor bearing temperature or an alternative temperature, such as liquid temperature. When MCB 114 has been installed, CUE automatically detects if the sensor is Pt100 or Pt1000 when it is switched on.
6.7.2 Fitting MCB 114 in CUE 7. Starting up the product Enclosures B2, C1 Any installation, maintenance and inspection must be car- 1. Switch off the power to CUE. See section RFI filter type is ried out by trained persons. according to EN 61800-3..
8. Control functions Pos. Buttons Description [Alarm] A fault condition causes the red alarm light The display contrast can be adjusted by pressing [Status] to flash and an alarm text is displayed. and then pressing [Up] or [Down]. When warning conditions are met, the yel- [Warn.] low warning light comes on and text ap- 8.1 Operating panel...
8.4.2 Controlled operation (closed loop) Operating mode Description The pump is running in the operating mode se- Normal Proportional differ- lected. ential pressure. The pump has been stopped, and the green in- The differential Stop dicator light is flashing. pressure is re- Min.
9. Servicing the product CAUTION Electric shock Minor or moderate personal injury ‐ Before starting any work on the product, make sure that the power supply has been switched off and that it cannot be accidentally switched on. Section Installa- tion requirements.
10. Fault finding the product 10.1 Overview of warnings and alarms Type LED indicator Warning Yellow Alarm Flashing red Trip lock Yellow and red Number Description Warning Alarm Alarm, trip lock 10 V low ● Live zero error (●) (●) No motor (●) Mains phase loss...
Page 23
Number Description Warning Alarm Alarm, trip lock AMA motor too large ● AMA motor too small ● AMA parameter out of range ● AMA interrupted by user ● AMA timeout ● AMA internal fault ● ● Current limit ● External interlock ●...
Page 24
Number Description Warning Alarm Alarm, trip lock 2008 Too high bearing temperature ● ● 2010 Setpoint signal outside range ● 2011 Sensor 1 is outside range ● 2012 Sensor 2 is outside range ● 2013 Temperature sensor 1 is outside range ●...
11. Technical data 11.3.4 Non-UL fuses and conductor cross-section to mains and motor, for installations outside North America 11.1 Enclosure Maximum conductor Typical shaft Maximum Fuse power P2 fuse size type cross-section Typical shaft power P2 Enclosure (3 x 380-500 V, IP55) [kW (hp)] [kW] [hp]...
This product or parts of it must be disposed of in an environmentally sound way. 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. The crossed-out wheelie bin symbol on a product means that it must be disposed of separately from household waste.