27. Technical data, three-phase motors

27.1 Supply voltage

Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
Recommended fuse size
3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE.
Motor size
[kW]
0.25 - 1.1
1.5
2.2
3
4
5.5
7.5
11
3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Motor size
[kW]
1.1
1.5
2.2
3
4
5.5
You can use standard as well as quick-blow or slow-
blow fuses.
Minimum
Maximum
[A]
[A]
6
6
6
10
6
16
10
16
13
16
16
32
20
32
32
32
Minimum
Maximum
[A]
[A]
10
20
10
20
13
35
16
35
25
35
32
35

27.2 Leakage current, AC

Speed
Power
-1
[kW]
[min
]
0.25 - 1.5
1400-2000
2.2 - 4
1450-2200
5.5 - 7.5
0.25 - 2.2
2900-4000
3 - 5.5
7.5 - 11
0.25 - 2.2
4000-5900
3 - 5.5
7.5 - 11
The leakage currents are measured without any load
on the shaft and in accordance with EN
61800-5-1:2007.
Mains
Leakage
voltage
current
[V]
[mA]
≤ 400
< 3.5
> 400
< 5
≤ 400
< 3.5
> 400
< 3.5
≤ 400
< 3.5
> 400
< 5
≤ 400
< 3.5
> 400
< 5
≤ 400
< 3.5
> 400
< 3.5
≤ 400
< 3.5
> 400
< 5
≤ 400
< 3.5
> 400
< 5
≤ 400
< 3.5
> 400
< 3.5
≤ 400
< 3.5
> 400
< 5