GRUNDFOS INSTRUCTIONS TPE, TPED Series 1000; NBE, NBGE, MTBE, NKE, NKGE; TPE, TPED, NBE, NKE Series 2000 Installation and operating instructions TPE, TPED Series 1000; NBE, NBGE, MTBE, NKE, NKGE; TPE, TPED, NBE, NKE Series 2000 Installation and operating instructions...
Page 3
TPE, TPED Series 1000; NBE, NBGE, MTBE, NKE, NKGE; TPE, TPED, NBE, NKE Series 2000 English (GB) Installation and operating instructions ........5 Български...
Page 4
Português (PT) Instruções de instalação e funcionamento ......1493 Română (RO) Instrucţiuni de instalare şi utilizare ........1582 Srpski (RS) Uputstvo za instalaciju i rad .
In some cases, an external antenna may be required. single-fault conditions, except earth Only Grundfos-approved external antennas may be faults in other circuits. connected to this product, and only by a Grundfos- approved installer. Residual-current device Related information A.1. Installation in the USA and Canada...
5.2 Inspecting the product Before you install the product, do the following: 1. Check that the product is as ordered. 2. Check that no visible parts have been damaged. If parts are damaged or missing, contact your local Grundfos sales company.
See page Installation in the Grundfos does not supply covers. We therefore USA and Canada. recommend that you have a cover built for the specific application.
7. Electrical installation 7.2 Cable requirements 7.2.1 Cable cross-section DANGER Electric shock DANGER Death or serious personal injury Electric shock ‐ Switch off the power supply to the Death or serious personal injury motor and to the signal relays. Wait at ‐...
Page 11
If you are in doubt, pulled out of the cable entry. contact Grundfos. In order to avoid loose connections, ensure that the terminal block for L1, L2 and L3 is pressed home in...
The motor is protected against transients from the power supply according to EN 61800-3. In areas with high lightning intensity, we recommend external lightning protection. Overload protection If the upper load limit is exceeded, the motor automatically compensates for this by reducing the speed and stops if the overload condition persists.
• Signal relay outputs • Input and output for Grundfos Digital Sensor Not Signal relay 1: applicable for TPE, TPED, NBE, NBGE, NKE and LIVE: You can connect supply voltages up to NKGE pumps. The factory-fitted differential- 250 VAC.
Page 14
+24 V* DI4/OC2 Pt100/1000 Pt100/1000 +5 V* +24 V* +24 V* +24 V*/5 V* LiqTec LiqTec +24 V* DI3/OC1 +24 V* +24 V* +24 V*/5 V* +5 V GENIbus A GENIbus Y GENIbus B +24 V +24 V +5 V GDS TX +24 V* +24 V*...
Page 15
Supply to potentiometer +5 V and sensor Pt100/1000 Pt100/1000 sensor input input 2 Earth Pt100/1000 Pt100/1000 sensor input Grundfos Digital Sensor input 1 GDS TX output Analog output: Grundfos Digital Sensor GDS RX 0-20 mA / 4-20 mA input 0-10 V...
7.6 Signal cables 7.7.2 Replacing a motor • If you have used a screened 2-core cable in the • Use screened cables with a cross-sectional area existing installation, connect the cable as shown of minimum 0.5 mm and maximum 1.5 mm below.
P2, at 50 °C, but continuous operation at higher Pos. Description temperatures reduces the expected product life. If the motor is to operate at ambient temperatures between Supply voltage [V] 50 and 60 °C, select an oversized motor. Contact Altitude [m] Grundfos for further information.
Remote controls 1500 2500 3500 • Grundfos GO. See section Grundfos GO. Supply voltage for single-phase motor in relation to If the power supply to the pump is switched off, the altitude settings are stored. Related information Pos. Description 10. Standard control panel...
Shows the operating status of setpoint set. the pump. 10.1.1 Pump in differential-pressure control mode See section Grundfos Eye for further information. The following example applies to a pump in an application where a pressure sensor gives a feedback Light fields for indication of to the pump.
Page 20
The figure below shows that the top light field is You can also stop the pump with the Grundfos GO or flashing, indicating maximum curve. via a digital input set to External stop. See section Priority of settings.
Saves changed values, resets alarms and expands the value Advanced control panel field. Enables radio communication with Grundfos GO and other products of the same type. When you try to establish radio communication between the pump and Grundfos GO or...
Related information 13.28 "Buttons on product" (Enable/disable settings) Stat 16. Priority of settings Pos. Symbol Description Setpoint 17. Grundfos Eye Home 5.00 bar This menu shows up to four user-defined parameters. You can select parameters shown as shortcut icon , and when Operaring mode...
Status Settings Assist Setpoint Control mode 5.00 bar Status Settings Assist Const. pressure Pos. Symbol Description Indicates that the pump is Setpoint Control mode functioning as master pump in a 5.00 bar Const. pressure multipump system. Operaring mode Actual controlled value Status Settings Assist Indicates that the pump is Normal...
11.3 Menu overview for advanced control panel 11.3.1 Main menus TPE, TPE, TPED, TPED, NBE, NBE, Multipump Home NBGE, system NKE, Series NKGE 2000 ● ● ● TPE, TPE, TPED, TPED, NBE, NBE, Multipump Status NBGE, system NKE, Series NKGE 2000 Operating status ●...
Page 26
TPE, TPED, TPE, TPED, Settings NBE, NBGE, NBE, NKE Multipump system Section NKE, NKGE Series 2000 Digital inputs ● ● ● Digital Digital input 1, setup ● ● ● inputs Digital input 2, setup ● ● ● Digital inputs/outputs ● ●...
Page 27
TPE, TPED, TPE, TPED, Settings NBE, NBGE, NBE, NKE Multipump system Section NKE, NKGE Series 2000 Communication ● ● ● "Number" Pump number ● ● ● (Pump number) "Radio communic ation" Enable/disable radio comm. ● ● ● (Enable/ disable radio comm.) General settings ●...
Page 28
TPE, TPED, TPE, TPED, Assist NBE, NBGE, NBE, NKE Multipump system Section NKE, NKGE Series 2000 Assisted Assisted pump setup ● ● ● pump setup Setup, analog Setup, analog input ● ● ● input "Multipump setup" (Setup Setting of date and time ●...
12.1 Communication When Grundfos GO initiates communication with the The pump is designed for wireless radio or infrared pump, the indicator light in the middle of Grundfos communication with Grundfos GO. Eye flashes green. See section Grundfos Eye. Grundfos GO enables setting of functions and gives...
12.2 Menu overview for Grundfos GO TPE, TPED, TPE, TPED, Multipump Dashboard NBE, NBGE, NBE, NKE system NKE, NKGE Series 2000 ● ● ● TPE, TPE, TPED, TPED, NBE, Multipump "Status" NBE, NKE NBGE, system Series NKE, 2000 NKGE "System mode"...
Page 31
Series NKE, 2000 NKGE "Pump 2" ● "Pump 3" ● "Pump 4" ● Only available if Grundfos GO is connected to a multipump system. TPE, TPED, TPE, TPED, Multipump "Settings" NBE, NBGE, NBE, NKE Section system NKE, NKGE Series 2000 "Setpoint"...
Page 32
"Connection code" ● ● ● "Connection code" "Unit "Unit configuration" ● ● ● configuration" (Units) Only available if Grundfos GO is connected to a multipump system. Applies only to a multipump system with TPE, TPED, NBE, NKE Series 2000 pumps.
This menu is only available in the advanced control • Max. Use the maximum-curve mode in periods in panel. With Grundfos GO, you set the speed via the which a maximum flow is required. This operating Setpoint menu. mode is for instance suitable for systems with hot- water priority.
Page 36
13.5.2 "Constant pressure" Related information 13.14 "Controller" ("Controller settings") 13.41 Assisted pump setup Pump variant "Constant pressure" TPE, TPED, NBE, 13.5.3 "Constant temperature" ● NBGE, NKE, NKGE TPE, TPED, NBE, NKE Pump variant "Constant temperature" ● Series 2000 TPE, TPED, NBE, ● NBGE, NKE, NKGE We recommend this control mode if the pump is to TPE, TPED, NBE, NKE...
Page 37
Controller settings For recommended controller settings, see section "Controller" ("Controller settings"). Related information 13.14 "Controller" ("Controller settings") 13.5.4 "Constant differential pressure" "Constant differential Pump variant pressure" TPE, TPED, NBE, ● NBGE, NKE, NKGE TPE, TPED, NBE, NKE ● Series 2000 Two external pressure sensors. The pump maintains a constant differential pressure, Constant differential-pressure control is achievable independently of the flow in the system.
You can set the analog inputs via the Setup, analog input menu. See section "Setup, analog input". If you perform the manual setting via Grundfos GO, you need to enter the menu for the analog input under the Settings menu.
Page 41
Measured parameter Parameter Possible measuring units Select one of the parameters, such as the parameter Pressure bar, m, kPa, psi, ft to be measured in the system by the sensor connected to the actual analog input. Level m, ft, in Flow rate /h, l/s, yd /h, gpm...
Built-in Grundfos sensor menu. sensor connected to the actual Pt100/1000 input. If you perform the setting manually via Grundfos GO, you need to enter the menu for the Built-in Grundfos sensor under the Settings menu. Function You can set the built-in sensor to these functions: •...
13.10 Digital inputs When this function has been selected, the accumulated flow can be registered. This requires the use of a flowmeter which gives a feedback Pump variant Digital inputs signal as a pulse per defined flow of water. See section "Pulse flowmeter setup".
Factory setting Function See section Factory settings. You can set the digital input or output 3 and 4 to these functions: Related information Possible functions, digital input or output 3 7.5.1 Connection terminals, advanced functional module, FM 300 Function if output Function if input 13.16.2 "Predefined setpoints"...
It is the time which, together with the mode, Function Terminal* determines how long the selected function is active. Relay output 1 NC, C1, NO Range: 0 to 15,000 seconds. Relay output 2 NC, C2, NO T input > T1 + T2 T input <...
13.13 Analog output Resulting setpoint Signal range Pump variant Analog output [V, mA] TPE, TPED, NBE, 0-10 V 10 V ● NBGE, NKE, NKGE 0-20 mA 0 mA 20 mA TPE, TPED, NBE, NKE ● 4-20 mA 4 mA 20 mA Series 2000 The reading is a percentage of the external setpoint Function...
Flow rate "Differential-pressure Signal control" range [V, mA] 0-10 V 10 V 0-20 mA 0 mA 10 mA 20 mA 4-20 mA 4 mA 12 mA 20 mA The reading is a percentage of the range between 0 and 200 % of the nominal flow. Factory setting See section Factory settings.
Rules of thumb "Differential-temperature control" If the controller is too slow-reacting, increase the gain. If the controller is hunting or unstable, dampen the system by reducing the gain or increasing the integral time. Factory setting See section Factory settings. -0.5 10 + 5L2 Related information 30. Factory settings...
13.16 External setpoint function Pos. Description Fixed maximum speed External setpoint Pump variant User-set maximum speed function "Operating range" TPE, TPED, NBE, ● NBGE, NKE, NKGE User-set minimum speed TPE, TPED, NBE, NKE Fixed minimum speed ● Series 2000 Factory setting You can influence the setpoint by an external signal, See section Factory settings.
Page 50
Related information Pos. Description 13.7 Analog inputs Actual input signal, 60 % 13.9 Pt100/1000 inputs External setpoint signal 30. Factory settings Setpoint 13.16.1 Setpoint influence Sensor max. Pump variant Setpoint influence Sensor min. TPE, TPED, NBE, Actual setpoint ● NBGE, NKE, NKGE TPE, TPED, NBE, NKE Example with constant curve with linear influence ●...
Page 51
Pos. Description Setpoint influence [%] External input • Linear with Stop In the input signal range from 20 to 100 %, the setpoint is influenced linearly. If the input signal is below 10 %, the pump changes to operating mode Stop. If the input signal is above 15 %, 100 % the operating mode is changed back to 3.5 V...
"User-defined speed" The pumps runs at a speed If all digital inputs are open, the pump either stops or set by the user. runs at the normal setpoint. Set the desired action with Grundfos GO or with the advanced control panel. Factory setting See section Factory settings.
13.18 "Pulse flowmeter setup" "Detection delay" You can set a detection delay which ensures that the monitored parameter stays above or below a set limit "Pulse flowmeter in a set time before the function is activated. Pump variant setup" "Resetting delay" TPE, TPED, NBE, ●...
13.20 "Standstill heating" Pump variant "Standstill heating" TPE, TPED, NBE, ● NBGE, NKE, NKGE TPE, TPED, NBE, NKE ● Series 2000 You can use this function to avoid condensation in humid environments. When you set the function to "Active" and the pump is in operating mode Stop, a low AC voltage is applied to the motor windings.
13.24 "Radio communication" (Enable/ "Time until next service" (Motor bearing service) disable radio comm.) This display shows when to replace the motor bearings. The controller monitors the operating pattern of the motor and calculates the period "Radio between bearing replacements. Pump variant communication"...
Operaring mode Actual controlled value Normal 4.90 bar button always remains active but you can only unlock all other buttons on the pump with Grundfos Pump variant "Store settings" TPE, TPED, NBE, Factory setting ● NBGE, NKE, NKGE See section Factory settings.
You can always modify the default connection code by pressing [Delete] and entering a new one. Pump variant "Pump name" If Grundfos GO fails to connect and ask you to press TPE, TPED, NBE, ● the connection button on the product, it means that...
Example of how to use the Assisted pump setup ("Controller settings"). for setting up the pump to constant pressure: 11. Check the summary of settings and confirm them by pressing [OK]. Grundfos GO 1. Open the Assist menu. Related information 2. Select Assisted pump setup. 13.1 Setpoint 3.
Page 60
If the duty pump stops due to a fault, the section "Assisted pump setup". backup pump starts automatically. 4. Assign a pump name to the pump using Grundfos 13.43.3 Cascade operation GO. See section "Pump name". Cascade operation ensures that the pump performance is automatically adapted to the 5.
Page 61
Alternating operation, Backup section "Assisted pump setup". operation and Cascade operation. 5. Assign a pump name to the pump using Grundfos 8. Press [>] three times to continue. GO. See section "Pump name". 9. Press [OK] to search for other pumps. The green 6.
16. Press [OK]. The multipump function icons appear in the bottom of the control panels. Pump variant Assisted fault advice The multipump system has now been set. Disabling the multipump function via Grundfos TPE, TPED, NBE, ● NBGE, NKE, NKGE 1. Select the "Assist" menu.
14. Selection of control mode System application Select this control mode In systems with relatively large pressure losses in the distribution pipes and in air-conditioning and cooling systems. • Two-pipe heating systems with thermostatic valves and the following: very long distribution pipes strongly throttled balancing valves Proportional pressure differential-pressure regulators...
15. Bus signal The pump supports serial communication via an RS-485 input. The communication is carried out according to the Grundfos GENIbus protocol and enables connection to other pumps as well as a building management system or another external control system.
"Start" "Start" *"Stop" and "Max. speed" settings made with Grundfos GO or on the motor control panel can be overruled by another operating-mode command sent from a bus, for example "Start". If the bus communication is interrupted, the motor resumes its previous operating mode, for example "Stop",...
17. Grundfos Eye The operating condition of the pump is indicated by the Grundfos Eye on the control panel. Grundfos Eye Grundfos Eye Indication Description The power is off. No lights are on. The pump is not running. The two opposite green indicator lights The power is on.
Page 67
Grundfos GO via radio connection. The green indicator light in the middle Remote control with Grundfos flashes quickly while Grundfos Go is GO via infrared light. exchanging data with the pump. It takes a few seconds. The pump is receiving data from Grundfos GO via infrared communication.
The pump has two outputs for potential-free signals via two internal relays. You can set the signal outputs to Operation, Pump running, Ready, Alarm and Warning. Contact position of signal relays when activated Operating Description Grundfos Eye mode Operation Running Ready Alarm Warning The power is off.
Page 69
Contact position of signal relays when activated Operating Description Grundfos Eye mode Operation Running Ready Alarm Warning Warning, but the pump was stopped via a "Stop" "Stop" command. Yellow, steady "Normal", Alarm, but the "Min." or pump is running. "Max."...
19. Installing a communication 1. Loosen the four screws (A) and remove the terminal box cover (B). interface module DANGER Electric shock Death or serious personal injury ‐ Switch off the power supply to the motor and to the signal relays. Wait at least 5 minutes before starting any work on the motor.
Page 71
4. Fit the CIM module by aligning it with the three 8. Route the wires for the CIM module. See the plastic holders (A) and the connecting plug (B). example below. Press home the module using your fingers. Fitting the CIM module 5.
You can identify the fitted module in one of the You can identify the fitted module in one of the following ways: following ways: Grundfos GO Grundfos GO You can identify the functional module in the Fitted You can identify the control panel in the "Fitted modules menu under Status.
22. Changing the position of the 3. Press and hold in the two locking tabs, A, while gently lifting the plastic cover, B. control panel DANGER Electric shock Death or serious personal injury ‐ Switch off the power supply to the motor and to the signal relays.
Earth leakage current less than 10 mA, DC. 23.2 Pump The leakage currents are measured in accordance with EN 61800-5-1:2007. Service documentation is available in Grundfos Product Center (http://product- selection.grundfos.com/). If you have any questions, please contact the nearest Grundfos company or service workshop.
27. Technical data, three-phase motors 27.2 Leakage current, AC 27.1 Supply voltage Mains Leakage Speed Power Check that the supply voltage and frequency voltage current [kW] [min correspond to the values stated on the nameplate. [mA] Recommended fuse size ≤ 400 <...
, 28-16 AWG. Screened cable: 0.5 - 1.5 mm , 28-16 AWG. Maximum cable length: 500 m. Grundfos Digital Sensor input and output, GDS* Analog inputs, AI Use Grundfos Digital Sensor only. Voltage signal ranges: *Not applicable for TPE, TPED, NBE, NBGE, NKE •...
1450-2000 min 4000-5900 min [Nm] 0.25 L1, L2, L3, L, N 2.35 0.37 NC, C1, C2, NO M2.5 0.55 1 to 26 and A, Y, B 0.75 C3/C1* C3/C1* C3/C1* C3/C1* C1, if equipped with an external Grundfos EMC filter.
31. Disposing of the product This product or parts of it must be disposed of in an environmentally sound way: 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop.
Page 81
Users are cautioned that changes or modifications type 3 and the product must be tested at a surface not expressly approved by Grundfos could void the temperature down to -35 °C. The MLE enclosure is user's authority to operate the equipment.
Page 82
A.1.4.3. Line reactors Maximum line reactor size must not exceed 1.5 mH. Maximum line reactor size in front of the drive must not exceed the following values: Maximum line reactor [mH] [kW] 1450-2000 rpm 2900-4000 rpm 1450-2200 rpm 4000-5900 rpm Identification numbers (1) 0.25 - 3 A.1.4.
Page 83
Argentina China Greece Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps (Shanghai) Co. Ltd. GRUNDFOS Hellas A.E.B.E. Ruta Panamericana km. 37.500industin 10F The Hub, No. 33 Suhong Road 20th km. Athinon-Markopoulou Av. 1619 - Garín Pcia. de B.A. Minhang District P.O. Box 71 Tel.: +54-3327 414 444...
Page 84
Fax: +66-2-725 8998 Fax: + 370 52 395 431 Москва, RU-109544, Russia Turkey Тел. (+7) 495 564-88-00 (495) 737-30-00 Malaysia GRUNDFOS POMPA San. ve Tic. Ltd. Факс (+7) 495 564 8811 GRUNDFOS Pumps Sdn. Bhd. Sti. E-mail grundfos.moscow@grundfos.com 7 Jalan Peguam U1/25 Gebze Organize Sanayi Bölgesi...